Conventional sprinklers
Hide thumbs Also See for G Series:

Advertisement

Quick Links

Features
Standard response
Conventional deflector
Robust solder capsule thermal element
Available in a wide variety of finishes
Product Description
Conventional (or "old-style" sprinklers) direct approximately 40%
of their water discharge up against the ceiling and the remainder
downward to the floor, and may be used in either the upright or
pendent position.
Reliable Model G Conventional Sprinklers are standard-response
fire sprinklers utilizing a solder capsule/strut and lever thermal
element.
These sprinklers are available in 4.10 (59.1 metric), 5.62 (81.0
metric), and 8.2 (118.2 metric) K factor.
When used in the pendent position, sprinklers may be installed
exposed or surface mounted using escutcheons such as the
Reliable Models B, C, or HB (reference Technical Bulletin 204).
Table A provides a summary of the approvals and availability of
specific Model G Series Conventional sprinkler configurations.
Additional technical information for each sprinkler model is
provided on the following pages.
Model G Series Conventional Sprinklers
Sprinkler
K-Factor gpm/psi
Model
(lpm/bar
4.10 (59.1)
G
5.62 (81.0)
8.2 (118.2)
1/2
Orientation
Response
)
1/2
Conventional
www.reliablesprinkler.com
K Factor 4.10 (59.1), 5.62 (81.0), and 8.2 (118.2)
Model G Conventional
Note: Not all versions of the sprinkler are shown.
Listings &
Approvals
Planiere Assemblee
LPCB, CE, Planiere
SR
Assemblee
LPCB, CE, Planiere
Assemblee
Bulletin 079 May 2021
Model G
Conventional Sprinklers
Table A
Sprinkler
Max. Working
Identification
Pressure psi (bar)
Number (SIN)
R1074
175 psi (12 bar)
R1075
R1077

Advertisement

loading
Need help?

Need help?

Do you have a question about the G Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Reliable G Series

  • Page 1 Note: Not all versions of the sprinkler are shown. exposed or surface mounted using escutcheons such as the Reliable Models B, C, or HB (reference Technical Bulletin 204). Table A provides a summary of the approvals and availability of specific Model G Series Conventional sprinkler configurations.
  • Page 2 Model G Conventional Sprinkler SIN R1074 Technical Specifications Sprinkler Finishes Style: Upright or Pendent (See Table B) Threads: 3/8” BPST Nominal K-Factor: 4.10 (59.1 metric) Sensitivity Max. Working Pressure: 175 psi (12 bar) Standard Response Temperature Ratings Material Specifications 135°F (57°C) Thermal Sensor: Solder Capsule 165°F (74°C) Sprinkler Frame: Leaded Red Brass Alloy...
  • Page 3 Model G Conventional Sprinkler SIN R1075 Technical Specifications Sprinkler Finishes Style: Upright or Pendent (See Table B) Threads: 1/2” BPST Sensitivity Nominal K-Factor: 5.62 (81.0 metric) Quick Response Max. Working Pressure: 175 psi (12 bar) Temperature Ratings 135°F (57°C) Material Specifications 165°F (74°C) Thermal Sensor: Solder Capsule 212°F (100°C)
  • Page 4 Model G Conventional Sprinkler SIN R1077 Technical Specifications Sprinkler Finishes Style: Upright or Pendent (See Table B) Threads: 3/4” BPST Sensitivity Nominal K-Factor: 8.2 (118.2 metric) Standard Response Max. Working Pressure: 175 psi (12 bar) Material Specifications Temperature Ratings Thermal Sensor: Solder Capsule 135°F (57°C) Sprinkler Frame: Leaded Red Brass Alloy 165°F (74°C)
  • Page 5: Installation

    For 212°F (100°C) maximum temperature rated sprinklers only. Model G series sprinklers must be installed with the Reliable Model Clear wax used on ordinary temperature rated sprinklers; W2 sprinkler installation wrench as identified in this Bulletin. Any other wrench may damage the sprinkler.

This manual is also suitable for:

R1074R1075R1077