Malfunctions And Potential Solutions - HOLLAND HEATER HHO 8L Installation And User Manual

Oil fired air heater
Table of Contents

Advertisement

7.4

Malfunctions and potential solutions

Malfunction :
Possible cause:
Solutions:
Malfunction :
Possible cause:
Solutions:
Malfunction :
Possible cause:
Solutions:
36
The air heater does not start, even when started manually.
The plug is not in the wall socket.
No mains voltage.
Faulty burner relay.
Master switch is switched off.
Maximum safety has been engaged.
Check the mains lead for breaks and/or insert the plug into the wall
socket.
Check that there is a current using a voltmeter. If not, check the voltage
circuit.
Replace the burner relay.
Reset the master switch.
Reset the maximum safety system.
The air heater does not respond to the heat demand of the thermostat
and 24 VDC drive. Manual ventilation and heating do work however.
No 24VDC drive.
Loose wiring.
Break in the system wiring.
24VDC relay is loose or faulty.
Faulty thermostat.
Faulty burner relay.
Check the 24VDC drive.
Repair loose wiring.
Check the system and repair the break in the wiring.
Replace the 24VDC relay.
Replace the thermostat.
Replace the burner relay.
The air heater does nothing. It is however connected to the mains
voltage and oil system.
Maximum safety has been engaged.
It is possible that the capacitor is faulty.
It is possible that one or more electrical components are faulty.
When restarting the appliance, check that the fan continues to ventilate
for 90 seconds afterwards.
Check that the fan is working.
If necessary, replace the fan or capacitor.
Remove any dirt from the grill in front of the fan.
Check that all electrical components are working correctly.
V16 HHO SERIES