HAUBER-Elektronik GmbH
12
Functional Description
Type 663-Window has two limit values, LIM1 and LIM2, with their respective lag times, which
can all be adjusted separately. If the value of the acceleration is below or above an adjustable
window-range, an alarm is generated. The lower limit of the window-range will be adjusted with
LIM1 and the upper limit with LIM2
In addition, Type 663-Window has an analogue current output. This delivers a direct current of
4...20 mA proportional to the vibration acceleration.
Fig. 6: User Interface Channels LIM1 and LIM2
1
SET Turn-Switch (Limit Value in 15 Steps)
2
TIME-Potentiometer (Lag Time Variably Adjustable, 0...30 sec.)
3
LED Indicators
Fig. 7: Window function
1
Alarm for values below LIM1
2
Window area
3
Alarm for values above LIM2
Only unscrew the housing cover if Type 663-Window is disconnected from the
mains or if the atmosphere is non-explosive. Otherwise, there is an explosion
hazard from sparking when operating ATEX-certified Type 663-Window in po-
tentially explosive atmospheres!!
11