3Ug4511 Line Monitoring Relay; Operator Controls And Connection Terminals; Function - Siemens SIRIUS 3UG4 Equipment Manual

Monitoring and control devices
Hide thumbs Also See for SIRIUS 3UG4:
Table of Contents

Advertisement

6.2

3UG4511 line monitoring relay

6.2.1

Operator controls and connection terminals

Front view / terminal labeling 3UG4511
Front view
L1
L2
L3
SIRIUS
3
160-260V
L1
L2
L3
11
12 14
3UG4511-.....
12
11
14
22
21
24
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 23)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 85)".
6.2.2

Function

General functionality
The 3UG4511 line monitoring relays monitor the phase sequence in a three-phase system.
The devices are self-powered (measuring voltage = rated control supply voltage) and work on
the closed-circuit principle. Depending on the version, the line monitoring relays are powered
with a rated control supply voltage of 160 V to 260 V (3UG4511‑..N20), 320 to 500 V
(3UG4511‑..P20) and 420 to 690 V (3UG4511‑..Q20) through terminals L1 / L2 / L3.
SIRIUS 3UG4 / 3RR2 monitoring relay
Equipment Manual, 07/2021, NEB927043002000/RS-AD/005
Description
Position digits
Terminal block (removable)
Connection is possible using screw-type terminals or spring-loaded terminals.
Circuit diagram
Device article number
Label
Status display: LED contact symbol (green)
Terminal labels
L1, L2, L3
Rated control supply voltage
12
Output relay K1 CO contact NC contact
11
Output relay K1 CO contact root
14
Output relay K1 CO contact NO contact
22
Output relay K2 CO contact NC contact (on the 3UG4511‑.B only)
21
Output relay K2 CO contact root (on the 3UG4511‑.B only)
24
Output relay K2 CO contact NC contact (on the 3UG4511‑.B only)
3UG4.1 line monitoring relay
6.2 3UG4511 line monitoring relay
83

Hide quick links:

Advertisement