The voltage source is the secondary side of an isolating transformer that galvanically isolates the system and the
downstream circuit.
The insulation resistance of this motor feeder is always monitored when the motor is switched off. If the motor
contactor drops out, the two NC contacts connect the measuring circuit with the motor cables.
The 3UG4583-.CW3. insulation monitoring relay permanently monitors the insulation resistance of the remaining
system with all connected loads.
Loads
Figure 9-11
Monitoring for ground fault/insulation fault with different load circuits
Note
The maximum cable length of the control cables is 50 m or 100 pF/m.
9.4.6

Characteristics

Characteristics of the 3UG4582 insulation monitoring relays
The characteristics below show the load limit curves of the 3UG4582 insulation monitoring
relays.
SIRIUS 3UG4 / 3RR2 monitoring relay
Equipment Manual, 07/2021, NEB927043002000/RS-AD/005
3UG458. insulation monitoring relay.
9.4 3UG4582/3UG4583 insulation monitoring relays