3UG458. insulation monitoring relay.
9.4 3UG4582/3UG4583 insulation monitoring relays
9.4.3

Operator control

Parameters
The following parameters can be set on the two (3UG4582) or four (3UG4583) ten-level rotary
buttons (absolute scale) with the help of a screwdriver:
Table 9-5
Parameter information, 3UG4582/3UG4583 insulation monitoring relays
Parameters
Threshold for undershoot
(R.1-value)
2)
Threshold for undershoot
(R.2-value)
3)
Threshold for undershoot
(R1.1-value)
4)
Threshold for undershoot
(R1.2-value)
5)
Threshold for undershoot
(R2.1-value)
6)
Threshold for undershoot
(R2.2-value)
7)
Test / Reset
The position digits refer to the front view of the respective 3UG4582 / 3UG4583 devices in
1)
Chapter "Operator controls and connection terminals (Page 170)".
3UG4582: By operating the rotary button, the tens position of the threshold for undershoot
2)
(R.1) can be selected.
3UG4582: By operating the rotary button, the units position of the threshold for undershoot
3)
(R.2) can be selected
3UG4583: By operating the rotary button, the tens position of the threshold for undershoot
4)
(R1.1) can be selected.
3UG4583: By operating the rotary button, the units position of the threshold for undershoot
5)
(R1.2) can be selected
3UG4583: By operating the rotary button, the tens position of the threshold for undershoot
6)
(R2.1) can be selected.
3UG4583: By operating the rotary button, the units position of the threshold for the insulation
7)
resistance R2.2 can be selected
The threshold is derived from the sum of the two set values. If, for example, threshold R.1-value
is set to 70 and threshold R.2-value is set to 8 on the 3UG4582, threshold R corresponds to
78 kΩ.
188
Control ele‐
Setting range
ments
1)
Minimum value
8
0 kΩ
7
1 kΩ
11
0 kΩ
9
1 kΩ
3
0 kΩ
7
1 kΩ
2 (3UG4582)
Deactivated
10 (3UG4583)
Maximum value
90 kΩ
10 kΩ
90 kΩ
10 kΩ
90 kΩ
10 kΩ
Activated
SIRIUS 3UG4 / 3RR2 monitoring relay
Equipment Manual, 07/2021, NEB927043002000/RS-AD/005
Increment
10 kΩ incre‐
ments
1 kΩ increments
10 kΩ incre‐
ments
1 kΩ increments
10 kΩ incre‐
ments
1 kΩ increments
--