Weekly tests

Weekly tests
Every week during normal working hours the fire detection and alarm
system should be tested. It is important to inform the alarm receiving centre
of the fire test.
The weekly fire test can be carried out at a manual call point without
breaking the call point glass.
Insert the test key into the keyhole located on the bottom-centre front
face of the call point and turn the key one quarter of a turn clockwise.
Manual Call point
Test Key
The 'Zone indicators' are not applicable at a Vigilon Plus Network Node
1
Zones
Fault
1stFIRE:MCP:Zone 1
Power Fault
First Fire occurred at:
System Fault
Time: 13:43.10
Delay
Test
Disablement
At this point the test key is retained in the call point.
12
www.acornfiresecurity.com
Panel
buzzer
On
15:45
Wed
16
March 2016
Previous
Next
If applicable it indicates there is active Fire routing output
to Alarm Receiving Centre. Who would know this is a test
as they would have been advised before the weekly test.
www.acornfiresecurity.com
Check the alarms are sounding in the building
and an indication is given of the fire event.
Turn the test key anticlockwise one quarter of
a turn and remove it from the call point.
With the panel door open:
To cancel
buzzer
To silence
alarms
Flashing
Fire
To reset
Verify
system
Sounder
Active
Fire
Routing
O/P
Fault/Dis
Power
Record
the event
You can stop the panel buzzer from
sounding.
CANCEL
BUZZER
Press:
Display reads: 'Buzzer cancelled'
When the test is complete, the alarm
sounders can be silenced.
SILENCE
ALARMS
Press:
Display reads: 'Alarms silenced'
To return the system to normal
condition clear any residual smoke
or heat from sensors and reset
element or replace the glass in any
manual call point where the glass
was broken.
RESET
Press:
Display reads:
'System being Reset - please wait....'
Make an entry in the log book of the
event for future reference.

Hide quick links: