Configuring level measurement via operating software

 24
Configuration parameters for level measurement in liquids
R
Reference point of measurement
D
Distance
L
Level
E
Empty calibration (= zero point)
F
Full calibration (= span)
BD Blocking distance
9.2.1
Via SmartBlue
1.
Navigate to: Setup → Distance unit
 Select unit of length for distance calculation
2.
Navigate to: Setup → Empty calibration
 Specify empty distance E (distance from reference point R to minimum level)
3.
Navigate to: Setup → Full calibration
 Specify full distance F (span: max. level - min. level)
4.
Navigate to: Setup → Distance
 Shows the distance D that is currently measured from the reference point (lower
edge of flange / last sensor thread) to the level
5.
Navigate to: Setup → Confirm distance
 Compare the distance displayed with the actual value in order to start the recording
of an interference echo map
6.
Navigate to: Setup → Mapping end point
 This parameter determines the distance up to which the new mapping is to be
recorded
Endress+Hauser
R
BD
D
E
F
L
Commissioning and operation
100%
0%
A0028417
31