Configuring Level Measurement Via Operating Software; Via Smartblue - Endress+Hauser Micropilot FMR20 Operating Instructions Manual

Modbus rs485 free space radar
Hide thumbs Also See for Micropilot FMR20:
Table of Contents

Advertisement

Micropilot FMR20 MODBUS RS485
Endress+Hauser
1
 23
Envelope curve display (sample) in SmartBlue for iOS
1
Record video
2
Create screenshot
3
Display mapping menu
4
Start/stop video recording
5
Move time on time axis
9.3
Configuring level measurement via operating
software
 24
Configuration parameters for level measurement in liquids
R
Reference point of measurement
D
Distance
L
Level
E
Empty calibration (= zero point)
F
Full calibration (= span)
BD Blocking distance
9.3.1

Via SmartBlue

1. Navigate to: Setup → Distance unit
 Select unit of length for distance calculation
2. Navigate to: Setup → Empty calibration
 Specify empty distance E (distance from reference point R to minimum level)
3. Navigate to: Setup → Full calibration
 Specify full distance F (span: max. level - min. level)
R
BD
D
E
F
L
Commissioning and operation
2
3
4
5
100%
0%
A0029487
A0028417
29

Advertisement

Table of Contents
loading

Table of Contents