F116 (SERIES 16000) SELF-CONTAINED DUCTABLE COMMERCIAL AIR CLEANER
BLOWER
MOTOR
Fig. 18. F116E1001 and F116E1100 (series 16000 and 16010) air cleaner typical wiring diagram.

SERVICE

IMPORTANT
Air cleaners and components are susceptible to
damage. Take care when working with them to avoid
equipment damage. Detergents used for washing
the electronic cells (if used) must never be acid
based and must have inhibitors to prevent cell
erosion.
The air cleaner removes a variety of particulate contaminants
from the air. In the process of cleaning the air, the air cleaner
filters become dirty and the cleaning efficiency is lowered.
To maintain a high standard of reliability and efficiency, it is
necessary to periodically service the air cleaner. The
maintenance is determined by the quantity and type of
contaminants present and the frequency of air cleaner use.
The cell performance indicator is on when the primary filters
need to be replaced or cleaned. The frequency of servicing
can only be established after a period of use.
NOTE: Some full-service distributors provide regular
servicing to commercial establishments.
CAUTION
• Turn off power to the air cleaner.
• Stand on a stable platform when working
with the air cleaner.
68-0200
POWER PACK LID
WHITE (COMMON)
N
BLACK (HIGH)
BLUE (MEDIUM)
RED (LOW)
L
BROWN
BROWN
OIL FILLED CAPACITOR —
CHECK NAMEPLATE FOR
CORRECT VALUE
DOOR INTERLOCK SWITCHES
TO CELL GROUND CONNECTION
GROUND
120 VAC
LINE
N
P3
P4
L
GRD
GRD
STUD
NC
NC
POWER PACK ENCLOSURE
C
C
NO
NO
Maintenance
1. Remove the air cleaner cover and set it aside.
2. Remove the prefilter and primary filters.
3. Locate the blower/motor and apply 3 to 4 drops of light
weight oil to the shaft bearings.
NOTE: Shaft bearings need oil once a year or every 3
or 4 months when the air cleaner operates 24
hours a day.
4. Use a detergent moistened cloth to annually wipe out
the air cleaner cabinet.
Prefilter and Media Filters
1. Remove the air cleaner cover and set it aside.
2. Remove the prefilter and primary filters.
3. Check the prefilter and replace if it is fully coated with
dust and lint (approximately every 1 to 3 months).
4. Replace the CPZ™ modules when a continuous
noticeable odor is emitted from the air cleaner
(approximately every 4 to 12 months).
5. Replace the particle or HEPA filter when there is a
noticeable loss of air volume circulation (approximately
every 10 to 24 months).
6. Reassemble the air cleaner and turn the power on.
12