FASTEN SECURELY TO STRUCTURAL SUPPORT SYSTEM
I.E. BAR JOIST, CONCRETE SLAB, TIMBER FRAMING, ETC.
ALL EXTERNAL HARDWARE
FURNISHED BY OWNER.
THREADED
ROD
JAM
NUT
TOP OF
AIR CLEANER
CABINET
3/8 x 16T NUTS INSTALLED
IN CABINET CORNERS
Fig. 13. Fastening air cleaner to a structural support
system (bar joist, concrete slab or timber framing).
Install with Ducting
Use a transition or box plenum to attach the ducting to air
cleaner inlet. A transition plenum is preferred. See Fig. 14. A
diffusion screen must be installed when a box plenum is used.
See Fig. 15. A box plenum can accommodate more than one
inlet.
Fig. 14. Transition plenum connected to the
air cleaner inlet.
DIFFUSION
SCREEN
Fig. 15. Box plenum with diffusion screen and three inlets
connected to the air cleaner.
F116 (SERIES 16000) SELF-CONTAINED DUCTABLE COMMERCIAL AIR CLEANER
CHAIN
HEX BOLT
LOCK
WASHER
EYEBOLT
JAM NUT
3/8 x 16T
M10802
AIR CLEANER
M7793A
AIR
CLEANER
M10803
Use a square-to-round or square-to-square connection when
attaching the air cleaner outlet to the blower discharge
flange. See Fig. 16. The outlet connection can be used with
a Y-branch, distribution box or manifold as required.
Y-BRANCH
Fig. 16. Square-to-round connection attached to the air
cleaner outlet.
Wire
All wiring must comply with applicable codes and ordinances.
The power source must agree with the air cleaner electrical
rating (120 Vac, 60 Hz).
1. Connect the power. See Fig. 17 and 18.
IMPORTANT
Ground the air cleaner for proper operation and
safety.
2. Turn on the power and check that the blower operates
at all three speed settings.
3. Check that the ON indicator lights when the fan is
operating.
4. Turn off the power and install the filters in the cabinet.
NOTE: Select models have a disposable aluminum
spacer. The spacer is necessary only when
using the CPZ™ modules. All other filters need
to remove and save the spacer for future
needs.
5. Replace the air cleaner cover.
WHITE (COMMON)
BLACK (HIGH)
BLUE (MEDIUM)
BLOWER
RED (LOW)
MOTOR
BROWN
BROWN
OIL FILLED CAPACITOR —
CHECK NAMEPLATE FOR
CORRECT VALUE
Fig. 17. F116A1021, F116A1047 and F116A1120
series 16002, 16004 and 16012) air cleaner typical
wiring diagram.
11
AIR CLEANER
SQUARE-TO-ROUND
M7792A
CONNECTION
GROUND
120 VAC
LINE
GROUND
M10805
68-0200