VBZE218-324-430 Indoor Units AWSI- Outdoor Units JYDE009-H11 AWAU-VBZE218-H11 AWSI-JYDE012-H11 AWAU-VBZE324-H11 AWSI-JYDE018-H11 AWAU-VBZE430-H11 REFRIGERANT R410A HEAT PUMP SM YBZE H11 1-A.1 GB May -2013 Version:1...
Page 2
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by “Revision #” in the footer of each effected page (when none indicates any changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
INTRODUCTION INTRODUCTION General The VBZE DC inverter multisplits outdoor is a multi-tubing system with 2, 3 or 4 connected indoor units. The multi-split inverter is a high level technology product for residential and commercial application offering comfort, low noise operation and energy saves. Indoor JYDE series is high-wall mounted type indoor which are mainly designed for residential buildings.
Page 5
INTRODUCTION Indoor Unit The indoor unit is wall mounted, and can be easily fitted to many types of residential locations. It includes: • LED display • Variable speed with PG motor • Motorized flap • High efficiency filtration to ensure a best Air Quality: Advanced filtering combine mechanical, Photo-catalytic + Bi-anti bacterial and observe bad gaseous and smokes.
Page 6
INTRODUCTION Outdoor Unit The outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti-corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
Page 7
INTRODUCTION Matching Table INDOOR UNITS AWSI-JYDE009-H11 AWSI-JYDE012-H11 AWSI-JYDE018-H11 OUTDOOR UNITS AWAU-VBZE218-H11 AWAU-VBZ324-H11 AWAU-VBZ430-H11 Indoor unit combination AWAU-YBZE218-H11 1 unit 2 units 9+12 AWAU-YBZE324-H11 2 units 3 units 9+12 9+9+9 9+9+12 9+9+18 9+18 12+12 9+12+12 12+12+12 9+12+18 12+18 12+12+18 AWAU-YBZE430-H11 2 units...
PRODUCT DATA SHEET PRODUCT DATA SHEET Model Outdoor Unit AWAU-VBZE218-H11 Installation Method of Pipe Flared Heating Characteristics Units Cooling Average Capacity (1) 5,0(2,05-6,2) 5,6(2,5-6,65) Pdesign SEER / SCOP (2) Energy efficiency class Annual energy consumption 1695 Tbiv ºC ºC Power supply V/Ph/Hz 220-240V/Single/50Hz Circuit breaker rating...
Page 9
PRODUCT DATA SHEET Model Outdoor Unit AWAU-VBZE324-H11 Installation Method of Pipe Flared Heating Characteristics Units Cooling Average Capacity (1) 7,1(2,2-10) 8,5(3,6-11) Pdesign SEER / SCOP (2) Energy efficiency class Annual energy consumption 2579 Tbiv ºC ºC Power supply V/Ph/Hz 220-240V/Single/50Hz Circuit breaker rating Refrigerant control Compressor type, model...
Page 10
PRODUCT DATA SHEET Model Outdoor Unit AWAU-VBZE430-H11 Installation Method of Pipe Flared Heating Characteristics Units Cooling Average Capacity (1) 8,0(2,2-10,0) 9,3(2,8-11,0) Pdesign SEER / SCOP (2) Energy efficiency class Annual energy consumption 2579 Tbiv ºC ºC Power supply V/Ph/Hz 220-240V/Single/50Hz Circuit breaker rating Refrigerant control Compressor type, model...
Page 11
PRODUCT DATA SHEET Model Indoor Unit AWSI-JYDE009- Installation Method of Pipe N11 Flared Characteristics Units Cooling Heating Capacity (4) 220-240 Power supply Fan type & quantity Crossflow x 1 Cooling SH/H/M/L 1350/1100/900/700 Fan speeds Heating SH/H/M/L 1350/1140/980/820 Air flow (1) SH/H/M/L m3/hr 600/520/370/280...
Page 12
PRODUCT DATA SHEET AWSI-JYDE018-N11 Model Indoor Unit Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 220-240 Power supply Fan type & quantity Crossflow x 1 Cooling SH/H/M/L 1350/1100/950/800 Fan speeds Heating SH/H/M/L 1400/1200/1050/900 Air flow (1) SH/H/M/L m3/hr 800/680/560/460 External static pressure...
RATING CONDITIONS RATING CONDITIONS Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB Operating Limits R410A Indoor Outdoor Upper limit C DB 23...
ELECTRICAL DATA ELECTRICAL DATA MODEL VBZE218 VBZE324 VBZE430 To outdoor Power Supply 1PH-220-240V-50Hz Max Current, A Circuit Breaker, A Power Supply Wiring No. X 3x2.5 mm 3x4.0 mm 3x4.0 mm Cross Section mm Interconnecting Cable Model No. X 4x1.0 mm 4x1.0 mm 4x1.0 mm Cross Section mm...
CONTROL SYSTEM CONTROL SYSTEM 12.1 Electronic Control 12.1.1 Abbreviations Abbreviation Definition Air Condition Building Management System System Power Compressor Top Temperature sensor DC Inverter Electronic Expansion Valve Heating Element Human Machine Interface Heat Sink Temperature sensor Hertz (1/sec) – electrical frequency Indoor Coil Temperature (RT2) sensor Indoor Unit Micro Controller Unit...
Page 28
CONTROL SYSTEM 12.1.2 Compressor Frequency Control 12.1.2.1 Compressor frequency setting The Load calculation is done by each indoor unit controller, based on a PI control scheme which is based on the difference between SPT and RAT. ODU controller will decide the compressor frequency based on the total load from all the indoors. Compressor frequency will be limited within following ranges: Minimum Frequency (MinFreq) Maximum Frequency (MaxFreq) *...
Page 29
CONTROL SYSTEM 12.1.3 Indoor Fan Control 8 Indoor fan speeds are determined for each model. 4 speeds for COOL modes and 4 speeds for HEAT mode. Unit Model Mode Turbo(Super high) High Medium Cooling 1350 1100 Heating 1350 1140 Cooling 1350 1100 Heating...
Page 30
CONTROL SYSTEM 12.1.5.2 EEV initial value determination The EEV initial value (open loop) is determined according to the number of the active indoor units, mode, and the capacity code of the unit. 12.1.5.3 Balance time During the balance after SB the correction is not calculated. After that the correction value is updated every 5 seconds.
Page 31
CONTROL SYSTEM 12.3.2.2 Partial indoors to inactive Recalculate the load immediately, for Inactive indoors, EEV opening is set to 0 step. 12.3.3 RV is OFF in Cool Mode. 12.3.4 OFAN control during Cool Mode OFAN will start 5sec before compressor start. After starting, it will run at High speed for 3 mins, and then switch to the requested speed.
Page 32
CONTROL SYSTEM 12.4.2 Compressor’s action when Indoor changed to inactive (OFF or Thermo OFF) 12.4.2.1 All indoors to inactive Compressor stops immediately, OFAN stops after 1 min. 12.4.2.2 Partial indoors to inactive Recalculate the load immediately, for Inactive indoors, EEV opening will follow 12.1.5.5.
Page 33
CONTROL SYSTEM 12.5 Auto Cool/Heat Mode In AUTO mode, the system selects the running mode (COOL/HEAT/FAN) automatically according to the room temperature. The display shows the actual running mode and setting temperature. There will be 30s delay for mode conversion. 1.
Page 34
CONTROL SYSTEM 12.7.2 Indoor Coil Defrost Protection During cooling operation, the signals being sent from the indoor unit allow the operating frequency limitation and then prevent freezing of the indoor heat exchanger. Compressor will stop when ICT <= -1C for continuous 10sec. If the unit stops as such protection for 6 times (the counter will be cleared after the compressor has run for...
Page 35
CONTROL SYSTEM 12.7.4 Compressor over Heating Protection The Discharging temperature is used as the compressor’s internal temperature. If the discharge temperature rises above a certain level, the operating frequency upper limit is set to keep this temperature from going up further. Compressor frequency will be reduced when CTT reaches above 97C Compressor will stop when CTT reaches 110C If the unit stops as such protection for 6 times...
Page 36
CONTROL SYSTEM 12.7.6.2 Deicing Protection Procedure When starting deicing from Heat Mode, system will work as following: 1). Compressor stops. OFAN and RV will be OFF after 40s 3). Compressor starts and deicing time is counted. Compressor frequency will go to Deicing Frequency.
Page 37
CONTROL SYSTEM 12.7.11 Compressor overload protection If the compressor OLP is opened, the system will stop as protection If the OLP is resumed and compressor has stopped for 3min, the unit will be allowed to operate. If the unit stops as compressor overload protection occurred for times continuously (the counter will be cleared after the compressor has run for...
Page 38
CONTROL SYSTEM 12.9 Indoor Unit Controllers and Indicators The following is schematic drawing for the display: 1. Lights up when the Air Conditioner is connected to power and the mode is STBY. RUN INDICATOR 2. When the unit is turned on remotely, the RUN LED goes out while the current setting running mode is displayed COOL INDICATOR 1.
Page 39
CONTROL SYSTEM 12.9.1 Installation Test Installation test is to check any mistake in communication wiring or EEV wiring connections. Start Installation Test: RC setting: SPT=30, Cool Mode and press the button “-, +,-, +,-, +” continuously in 3 sec. Unit operation during Installation test: Unit will operate in cool mode (IFAN will stop), IDU will display “dd”.
TROUBLESHOOTING TROUBLESHOOTING 13.1 ELECTRICAL & CONTROL TROUBLESHOOTING 13.1.1 Precautions before Performing Inspection or Repair Be cautious during installation and maintenance. Do operation following the regulations to avoid electric shock and casualty or even death due to drop from high attitude. * Static maintenance is the maintenance during de-energization of the air conditioner.
Page 41
TROUBLESHOOTING 13.1.3 Fault Code display from ODU The ODU can not show fault directly, can only know whether there is fault status by Communication LED. (Fault status – LED ON 1sec, OFF 1sec. ) 13.1.4 Fault Code display from IDU If the malfunction still exists 4min later after stop of unit due to compressor protection, error code will be directly displayed though indoor display.
Page 42
TROUBLESHOOTING LEDs blinking 2* 7 Fault description Possible Reason segments RUN COOL HEAT 1. EEV connection problem or damaged Compressor overload 2. Refrigerant leakage protection 3. OLP damaged 1. EEV connection problem or damaged Compressor overload 2. Refrigerant leakage protection 3.
Page 43
TROUBLESHOOTING 13.1.5 Checking the refrigeration system Checking system pressures and other thermodynamic measures should be done when system is in Test Mode (in Test mode, system operates in fixed settings). The performance curves given in this manual are given for unit performance in test mode when high indoor fan speed is selected.
EXPLODED VIEW & SPARE PART LIST EXPLODED VIEW & SPARE PART LIST 15.1 Exploded view of indoor unit: JYDE009, JYDE012 15–1 Service Manual – VBZE DCI 1-A.1 GB...
Page 47
EXPLODED VIEW & SPARE PART LIST 15.2 Spare part list of indoor Unit: JYDE009 Part Code Part Description G1112208201 Filter Sub-Assy G20012806B Front Panel G24252019 Screw Cover none Membrane G20012824 Front Case Assy G10512119 Guide Louver G26112486 Helicoid tongue G10512160 Air Louver G1054202001 Shaft of Guide Louver...
Page 48
EXPLODED VIEW & SPARE PART LIST 15.3 Spare part list of indoor Unit: JYDE012 Part Code Part Description G1112208201 Filter Sub-Assy G20012806B Front Panel G24252019 Screw Cover G63022016 Membrane G20012824 Front Case Assy G10512119 Guide Louver G26112486 Helicoid tongue G10512160 Air Louver G1054202001 Shaft of Guide Louver...
Page 49
EXPLODED VIEW & SPARE PART LIST 15.4 Exploded view of indoor unit: JYDE018 Service Manual – VBZE DCI 1-A.1 GB 15–4...
Page 50
EXPLODED VIEW & SPARE PART LIST 15.5 Spare part list of indoor Unit: JYDE018 Part Code Part Description none Decorative Strip G20012872_K88497 Front Panel Assy G11122104 Filter Sub-Assy G242520041 Screw Cover G20012873 Front Case Assy G10512140 Guide Louver G10542036 Axile Bush G10512160 Air Louver G26112232...
Page 51
EXPLODED VIEW & SPARE PART LIST 15.6 Exploded view of outdoor unit: VBZE218 Service Manual – VBZE DCI 1-A.1 GB 15–6...
Page 52
EXPLODED VIEW & SPARE PART LIST 15.7 Spare part list of outdoor Unit: VBZE218 Part Code Part Description G22415002 Front Grill G01535013P Front Panel G02803263P Chassis Sub-assy G06123401 Drainage Connecter G06813401 Drainage Hole Cap G07225017 Gas-liquid Separator Assy G00105249G Compressor and Fittings G32003001 OH Thermistor(compressor) none...
Page 53
EXPLODED VIEW & SPARE PART LIST 15.8 Exploded view of outdoor unit: VBZE324 Service Manual – VBZE DCI 1-A.1 GB 15–8...
Page 54
EXPLODED VIEW & SPARE PART LIST 15.9 Spare part list of outdoor Unit: VBZE324 Part Code Part Description G22415003 Front Grill G01435004P Cabinet G26235401 Left Handle G01305086P Front Side Plate G7651000411 Electrical Heater (Chassis) G06123401 Drainage Connecter G02803280P Chassis Sub-assy G07225017 Gas-liquid Separator Assy G0010524501G...
Page 55
EXPLODED VIEW & SPARE PART LIST 15.10 Exploded view of outdoor unit: VBZE430 Service Manual – VBZE DCI 1-A.1 GB 15–10...
Page 56
EXPLODED VIEW & SPARE PART LIST 15.11 Spare part list of outdoor Unit: VBZE430 Part Code Part Description G22415003 Front Grill G01435004P Cabinet G26235401 Left Handle G01305086P Front Side Plate G7651000411 Electrical Heater (Chassis) G06123401 Drainage Connecter G02803280P Chassis Sub-assy G07225017 Gas-liquid Separator Assy G0010524501G...
Page 57
EXPLODED VIEW & SPARE PART LIST APPENDIX Service Manual – VBZE DCI 1-A.1 GB 15–12...