Table 1.Setting data(CODE No. table(example))
DN
Filter display delay timer
01
Dirty state of filter
02
Central control address
03
Specific indoor unit priority
04
Heating suction temperature shift
06
Automatic mode
0D
Cooling only
0F
Type
10
Indoor unit capacity
11
Line address
12
Indoor unit address
13
Group address
14
Flap type (Wind direction adjustment)
19
Temperature range of cooling/heating
1E
automatic SW control point
Automatic restart of power failure
28
Selection of option / Trouble input
2A
(TCB-PCUC2E: CN3)
Themo output SW
2B
HA terminal (CN61) select
2E
Ventilating fan control
31
Sensor SW
32
Temperature unit select
33
External static pressure
5D
Timer setting (wired remote controller)
60
7A
Remote controller operation save function
D0
E0
Region
Presence of Application control kit
F6
(TCB-PCUC2E)
FC
Communication protocol
FE
FS unit adress
1Fb
Remote controller operation
1FC
Indoor Unit terminating resistance
Table 2. Type : CODE No.10
Setting
Type
data
*1
4-way Air Discharge
0001
Cassette Type
*1
EEPROM initial value on the P.C. board for indoor unit
servicing.
*2
CAUTION
< Model name MMU-AP****HPUL >
For the above model. Set the CODE no. to
"E0" the setting data "0000" (initial) to "0001"
"28" the setting data "0000" (initial) to "0001"
"33" the setting data "0000" (initial) to "0001"
"7A" the setting data "0000" (initial) to "0001"
Item
Type name abb.
MMU-AP****HPUL
Setting data
0001 : Enable
0001 : North America
Table 3. Indoor unit capacity : CODE No.11
Setup data
Model
*1
0000
Invalid
0001
007 type
0003
009 type
0005
012 type
0007
015 type
0009
018 type
0011
024 type
0013
030 type
0015
036 type
0016
042 type
0017
048 type
0018
054 type
- 95 -
Factory-set value
0002 : 2500H
0000 : Standard
00Un/0099 : Unfixed
0000 : No priority
0001 : No automatic
0000 : Heat pump
Depending on model type
According to capacity type
00Un/0099 : Unfixed
00Un/0099 : Unfixed
00Un/0099 : Unfixed
Depending on Type
0000 : None
0002 : None
0000 : Thermo ON
0000 : Usual (HA terminal)
0000 : Unavailable
0000 : Body sensor
0000 : Default setting
0000 : Available
0001 : Enable
0000 : Japan model
0000 : None
0000 : TCC-LINK
00Un/0099 : Unfixed
0000 : Operation possible
0000 : OFF

Hide quick links: