Trane UniTrane FCD Installation Operation & Maintenance page 16

Ducted fan coil units
Table of Contents

Advertisement

16
Installation
Mount the unit, with a slight slope
towards the drain pan outlet as
shown in Figures 9 and 10. Ensure
that sufficient service access is
provided around the unit for
maintenance.
Figure 9
1 = Drain pan outlet
Figure 10
+ 2 mm
- 2 mm
CAUTION! If the unit is not
mounted with a slight slope, the
condensates will not drain correctly
through the hole provided. Refer to
Figures 9 and 10. In order to be sure
that the unit is correctly installed, it
is highly recommended to make a
test filling in the drain pan with
water and make sure that water
does not overflow.
UNT-SVX10G-E4