Samsung AM072/096/120/144FXVAFH Service Manual page 155

Table of Contents

Advertisement

Troubleshooting
: Suction Temperature sensor breakaway error
✳✳
AM038/048/055KXWD
Outdoor unit display
Operation Defrost
Indoorunit display
※ ● : ON ◑ : Flash × : OFF
∙ Difference of suction temperature of compressor starting verge and suction temperature that is on present operation :
Judgment Method
When less than 2
Cause of problem
∙ Suction temperature sensor breakaway / defective
1. How to check
Is suction sensor and sensor
holder accurately attached?
Is suction sensor resistance
value reasonable?
(Refer to E231)
4-58
Duct, Cassette (1/2 Way),Console, Celing
Timer
Fan
Filter/MPI Operation Defrost
×
×
for 30 minutes to keep. (Judgment at heating operation only)
Yes
Yes
Complete
(cont.)
Cassette (4/Mini4 Way)
Timer
Filter
18℃
×
×
No
Re-insert the sensor.
Reassemble the sensor holder.
No
Replace the defective sensor
Wall-mounted (NeoForte)
21℃
Turbo
24℃
27℃
×
Samsung Electronics