4-4-16 MCU/MCU subcooler entrance/exit sensor error (Open/Short)

Outdoor unit display
Duct, Cassette (1/2 Way),Console, Celing
Operation Defrost
Indoor Unit Display
×
※ ● : ON ◑ : Flash × : OFF
Judgment Method
∙ Refer to the judgement method below.
Cause of problem
∙ MCU/MCU subcooler entrance/exit sensor is open/short
1. Cause of problem
Is the sensor connector connected on the PCB ?
Separate the connector from the PCB and measure
the resistance value between the 2 terminals.
Is the resistor value matching
with "NOTE1" table?
Restart operation after replace the PCB
Samsung Electronics
(MCU subcooler)
(MCU)
Timer
Fan
Filter/MPI Operation Defrost
×
×
Yes
Yes
Yes
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Timer
Filter
Operation
No
Restart operation after connecting
the connector to PCB
Temperature(°C)
70
60
50
40
30
20
10
0
-10
No
Replace this part as it is the defective itself.
Troubleshooting
Timer
Turbo
NOTE1
Resistance(KΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0