Check Safety Controls - Bryant C Series Installation, Start-Up, And Operating Instructions Manual

Downflow gas-fired induced-combustion furnaces
Table of Contents

Advertisement

TABLE 7—GAS RATE CU FT/HR
SECONDS
SIZE OF TEST DIAL
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
WARNING: Disconnect the electrical power before
changing the speed tap. Failure to follow this warning
could result in personal injury.
d. To change motor speed taps, remove the motor tap lead
and relocate it on the desired terminal on the plug-in
terminal block/speed selector located on the blower
housing. (See Table 9.)
TABLE 8—CANADIAN ORIFICE SIZE
SEA LEVEL
GAS
0—2000
Natural
44
Propane
54
TABLE 9—SPEED SELECTOR
SPEED
Common
High
Med-High
Med-Low
Low
* White wire from control box to common; black wire from control box to cooling
speed selection; red wire from control box to heating and constant fan speed
selection.
SECONDS
SIZE OF TEST DIAL
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
50
72
144
360
51
71
141
355
52
69
138
346
53
68
136
340
54
67
133
333
55
65
131
327
56
64
129
321
57
63
126
316
58
62
124
310
59
61
122
305
60
60
120
300
62
58
116
290
64
56
112
281
66
54
109
273
68
53
106
265
70
51
103
257
72
50
100
250
74
48
97
243
76
47
95
237
78
46
92
231
80
45
90
225
82
44
88
220
84
43
86
214
86
42
84
209
88
41
82
205
90
40
80
200
92
39
78
196
94
38
76
192
96
38
75
188
98
37
74
184
100
36
72
180
102
35
71
178
104
35
69
173
106
34
68
170
108
33
67
167
110
33
65
164
112
32
64
161
116
31
62
155
120
30
60
150
HIGH ALTITUDE
2001—4500 FT
45
55
TAP NO.*
C
1
2
3
4
CAUTION: Recheck the temperature rise. It must be
within the limits specified on the unit rating plate.
Recommended operation is at midpoint of rise or above.
3. Set thermostat heat anticipator.
The thermostat heat anticipation must be set to match the
amp draw of the electrical components in the R-W circuit.
Accurate amp draw readings can be obtained at thermostat
subbase terminals R and W. Fig. 14 illustrates an easy
method of obtaining the actual amp draw. The amp reading
should be taken after the blower motor has started. See the
thermostat manufacturer's instructions for adjusting the
heat anticipator and for varying the heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3
cycles per hr.
Fig. 14—Amp Draw Check With Ammeter
E. Check Safety Controls
1. Check operation of gas shut-off control for 100 percent
shutoff.
NOTE: The furnace pilot must be lit so the thermocouple
5.0 AMPS ON AMMETER
EXAMPLE:
10 TURNS AROUND JAWS
energizes the thermal magnet circuit of gas valve GV, which
permits gas flow to the remaining portion of the valve.
If the pilot flame is extinguished, the thermocouple will no
longer energize the thermal magnet circuit of the gas valve.
Gas flow to the pilot and main burners will cease until the
pilot is manually relit.
a. With furnace operating, unscrew pilot thermocouple lead
from gas valve. The pilot and main burner gas must shut
off. No gas should flow through valve.
b. After valve is found to operate satisfactorily, reconnect
thermocouple to gas valve (fingertight position only).
c. Tighten thermocouple connection 1/4 turn with wrench.
d. Relight pilot by following lighting instructions on the
furnace.
2. Check primary limit control.
This control shuts off the combustion control system and
energizes the circulating-air blower motor if the furnace
overheats.
The preferred method of checking the limit control is to
gradually block off the return air after the furnace has been
operating for a period of at least 5 minutes. As soon as the
limit has shut off the burners, the return-air opening should
be unblocked. By using this method to check the limit
control, it can be established that the limit is functioning
properly and will operate if there is a motor failure.
3. Check draft safeguard switch.
—12—
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
HOOK-AROUND
VOLT/AMMETER
R Y W G
10 TURNS
FROM UNIT 24-VOLT
TERMINAL BLOCK
= 0.5 AMPS FOR THERMOSTAT SETTING
A80201