Chapter 8 Maintenance
circuit shouldn't be less than 3 MΩ.

8.1.3 Replace device at regular intervals

For security of the ac drive operation, to ensure the long term and reliable operation, the
lifetime of components used in the ac drive must be periodically maintained. The
lifetime of the component will be different because of the different environment and
conditions. For constant operation, users can follow the next table to replace the device.
In addition, the operation environment, load status and the current state should be
considered.
Parts
Cooling Fan
Electrolytic capacitor
Printed Circuit Board
Fuses

8.2 Storage and Keeping

After bought in, the ac drive needs to be stored temporarily of secularly if it isn't
immediately:
●Environmental temperature should be in the defined range. Prevent it from being in
contact with damp, dust powder, metal dirt; keep it in a draughty place.
●If stored period has exceeded one year, users should do charging experiment to recover
the characteristics of electrolytic capacitor. When charging, please use voltage
regulator to increase input voltage to rated voltage of the ac drive slowly and last the
charging 1~2 hours.
●Experiment described above should be done at least one time per year.
Voltage proof experiment will shorten life span of the ac drive. For the electric
insulation test, please choose 500V megohm-meter, Earth resistance should not be less
than 4 MΩ.
http://www.acdrive-china.com
208
Table 8-4 Parts Replacement Schedule
Standard replacing years
2~3years
4~5years
5~8years
10years