Altitude Derate Multiplier For U.s.a - Payne PG92ESA Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage 35-in. (889 mm) tall 4-way multipoise condensing gas furnace
Hide thumbs Also See for PG92ESA:
Table of Contents

Advertisement

motor failure. If the limit control does not function during
this test, the cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard or
sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re- -light when furnace cools down.
2. Check Pressure Switch(es)
This control proves operation of the draft inducer blower.
a. Turn off 115- -v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115- -v power to furnace.
d. Set thermostat to "call for heat" and wait 1 minute. When
low pressure switch is functioning properly, hot surface
igniter should NOT glow and control diagnostic light
flashes a status code 31. If hot surface igniter glows when
inducer motor is disconnected, shut down furnace immedi-
ately.
e. Determine reason low pressure switch did not function
properly and correct condition.
f. Turn off 115- -v power to furnace.
g. Reconnect inducer motor wires, replace door, and turn on
115- -v power.
h. Blower will run for 90 sec before beginning the call for
heat again.
i. Furnace should ignite normally.
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that the jumper is removed from the TEST/TWIN
terminal. Verify that there is nothing plugged into the PLT
connector. (Note: If there is a jumper connector plugged
into PLT, remove it and discard.) See Fig. 38.
3. Verify that the Blower/Heat Off Delay jumpers are set as
desired. See Fig. 38 and 72.
4. Verify that the blower (lower door in upflow position) and
control ("Main" or upper door in upflow position) doors are
properly installed.
5. Verify that the Status LED glows. If not, check that the
power supply is energized and that the blower door is
secure. See Fig. 65 to interpret diagnostic codes.
6. Cycle test furnace with room thermostat to be sure that it
operates properly with the room thermostat. Check all
modes including Heat, Cool and Fan.
7. Check
operation
instructions.
8. Review Owner's Manual with owner.
9. Attach entire literature packet to furnace.
Table 19 – Altitude Derate Multiplier for U.S.A.
ALTITUDE
FT.
0–2000
0--- 610
2001–3000
610--- 914
3001–4000
914--- 1219
4001–5000
1219--- 1524
5001–6000
1524--- 1829
6001–7000
1829--- 2134
7001–8000
2134--- 2438
8001–9000
2438--- 2743
9001–10,000
2743--- 3048
*Derate multiplier factors are based on midpoint altitude for altitude range.
68
of accessories
per manufacturer's
PERCENT
DERATE
OF
MULTIPLIER
M
DERATE
FACTOR*
0
4--- 6
6--- 8
8--- 10
10--- 12
12--- 14
14--- 16
16--- 18
18--- 20
1.00
0.95
0.93
0.91
0.89
0.87
0.85
0.83
0.81