Performance Data Sheet - A.O. Smith Pro AOW-4000 Owner's Manual

Reverse osmosis with microbial and pump
Table of Contents

Advertisement

Available languages

Available languages

14

PERFORMANCE DATA SHEET

Performance Data for the Drinking Water System AOW-4000
Models
Replacement
Operating
Operating temp.
pressure range
range
AOW-4000 AOW-4000-CARBON and
40-100 psi
40-100° F
AOW-4000-MEM
275-689 kPa
5-37° C
Manufactured by: A. O. Smith Corporation 11270 West Park Place | Milwaukee, WI 53224 | 877.333.7108
Testing Performed under NSF/ANSI Standards 42, 53, 58, 401 & P473 and in accordance with the California Department of Health Services
Drinking Water Treatment Device Program. This System has been tested according to NSF/ANSI 42, 53, 401 & P473 for reduction of the
substances listed below. The concentration of the indicated substances in water entering the System was reduced to a concentration less than or
equal to the permissible limit for water leaving the System, as specified in NSF/ANSI 42, 53, 58, 401 & P473.
NSF/ANSI 42
Minimum Reduction
Overall% Reduction
Chlorine Reduction, Free Available
<0.5 mg/l
60.20%
Particulate Reduction
85%
99.8%
NSF/ANSI 53
Minimum Reduction
Overall% Reduction
Cyst Live Cryptosporidium & Giardia
99.95%
>99.95%
Mercury Reduction pH 8.5
<2 ug/L
>96.7%
Mercury Reduction pH 6.5
<2 ug/L
>96.6%
Lead Reduction pH 6.5
<10 ug/L
>99.4%
Lead Reduction pH 8.5
<10 ug/L
>99.3%
MTBE Reduction
<5 ug/L
86.6%
Turbidity
<0.5 NTU
99.1%
VOC Surrogate Test
95%
99.4%
Asbestos
99%
>99%
Maximum Concen-
Minimum
NSF/ANSI 58
Overall% Reduction
tration
Reduction
Arsenic Pentavalent
0.30mg/L ± 10%
80.0%
98.0%
Barium
10.0mg/L ± 10%
80.0%
97.2%
Cadmium
0.30mg/L ± 10%
83.3%
98.2%
Chromium Hexavalent
0.30mg/L ± 10%
66.7%
98.2%
Chromium Trivalent
0.30mg/L ± 10%
66.7%
97.6%
Copper
0.30mg/L ± 10%
56.7%
98.8%
Fluoride
8.0mg/L ± 10%
81.2%
96.5%
Lead
.15mg/L ± 10%
93.3%
96.6%
Nitrate/Nitrite
30.0mg/L ± 10%
66.7%
95.9%
Selenium
0.10mg/L ± 10%
50.0%
98.0%
TDS
750mg/L ± 10%
75.0%
96.7%
Turbidity
11 ± NTU
95.4%
99.1%
Maximum
NSF/ANSI 401
Minimum Reduction
Overall% Reduction
Concentration
Atenolol
30 ng/L
94.2%
94.2%
Bisphenol A
300 ng/L
98.80%
98.9%
Carbamazepine
200 ng/L
98.6%
98.6%
DEET
200 ng/L
98.7%
98.7%
Estrone
20 ng/L
96.30%
96.5%
Ibuprofen
60 ng/L
95.3%
95.4%
Linuron
20 ng/L
96.6%
96.6%
Meprobamate
60 ng/L
94.7%
94.7%
Metolachlor
200 ng/L
98.6%
98.6%
Naproxen
20 ng/L
96.3%
96.4%
Nonyl phenol
200 ng/L
97.50%
97.5%
Phenytoin
30 ng/L
95.50%
95.6%
TCEP
700 ng/L
98%
98%
TCPP
700 ng/L
97.8%
97.8%
Trimethoprim
20 ng/L
96.7%
96.7%
Influent challenge
Maximum permissible
Overall%
NSF P473
concentration
concentration
reduction
Perfluorooctanoic
acid (PFOA) &
1.5 ±10% ug/L
0.07 ug/L
95.8%
Perfluorooctane
sulfonate (PFOS)
Filter is only to be used with cold water.
Filter usage must comply with all state and local laws.
Testing was performed under standard laboratory
conditions, actual performance may vary.
Systems certified for cyst reduction may be used on
disinfected waters that may contain filterable cysts.
See owner's manual for general installation conditions
and needs plus manufacturer's limited warranty.
• All contaminants reduced by this filter are listed.
• Not all contaminants listed may be present in your water.
• Does not remove all contaminants that may be present in tap water.
NEED HELP? GIVE US A CALL 833.232.9711
Recovery
Efficiency
Daily
rating
rating
Production (DPR)
47.66%
37.64%
83.93 gallons
317 liters
Results
Organic chemicals included by surrogate testing
Pass
VOCs
Drinking water
Influent/
(by surrogate testing
regulatory level (MCL/
Unfiltered
Pass
using chloroform)
MAC) mg/L
Results
alachlor
0.002
0.050
Pass
atrazine
0.003
0.100
benzene
0.005
0.081
Pass
carbofuran
0.04
0.190
Pass
carbon tetrachloride
0.005
0.078
Pass
chlorobenzene
0.1
0.077
Pass
chloropicrin
0.015
Pass
2,4-D
0.07
0.110
Pass
dibromochloropropane (DBCP)
0.0002
0.052
o-dichlorobenzene
0.6
0.080
Pass
p-dichlorobenzene
0.075
0.040
Pass
1,2-dichloroethane
0.005
0.088
1,1-dichloroethylene
0.007
0.083
Results
cis-1,2-dichloroethylene
0.07
0.170
Pass
trans-1,2-dichloroethylene
0.1
0.086
Pass
1,2-dichloropropane
0.005
0.080
Pass
cis-1,3-dichloropropylene
0.079
dinoseb
0.007
0.170
Pass
endrin
0.002
0.053
Pass
ethylbenzene
0.7
0.088
Pass
ethylene dibromide (EDB)
0.00005
0.044
Pass
haloacetonitriles (HAN)
Pass
bromochloroacetontrile
0.022
Pass
dibromoacetontrile
0.024
dichloroacetontrile
0.0096
Pass
trichloroacetontrile
0.015
Pass
haloketones (HK)
Pass
1,1-dichloro-2-propanone
0.0072
1,1,1-trichloro-2-propanone
0.0082
Results
heptachlor (H-34, Heptox)
0.0004
0.025
Pass
heptachlor epoxide
0.0002
0.0107
Pass
hexachlorobutadiene
0.044
Pass
hexachlorocyclopentadiene
0.05
0.060
lindane
0.0002
0.055
Pass
methoxychlor
0.04
0.050
Pass
pentachlorophenol
0.001
0.096
Pass
simazine
0.004
0.120
Pass
styrene
0.1
0.150
Pass
1,1,2,2-tetrachloroethane
0.081
Pass
tetrachloroethylene
0.005
0.081
Pass
toluene
1
0.078
2,4,5-TP (silvex)
0.05
0.270
Pass
tribromoacetic acid
0.042
Pass
1,2,4-trichlorobenzene
0.07
0.160
Pass
1,1,1-trichloroethane
0.2
0.084
Pass
1,1,2-trichloroethane
0.005
0.150
Pass
trichloroethylene
0.005
0.180
Influent/
trihalomethanes (THMs)
Results
Unfiltered
bromodichloromethane (THM)
bromoform (THM)
0.080
0.300
Pass
chloroform (THM)
chlorodibromomethane (THM)
xylenes (total)
10
0.070
System Tested and Certified by NSF International against
NSF/ANSI Standards 42, 53, 58 & 401 and conforms to
NSF protocol P473 for reduction of claims specified on the
Performance Data Sheet and at www.nsf.org.
COMPONENT
Remineralizer with Microbial Filter is Tested and
Certified by IAPMO R&T Lab and IAPMO R&T against NSF
Protocol P231 as verified and substantiated by test data.
El remineralizador con refuerzo microbiano está probado y certificado
por IAPMO R&T Lab y IAPMO R&T según el protocolo P231 de NSF
según se verifica y corrobora mediante los datos de prueba.
For use with municipally treated water only. Do not use with
water that is microbiologically unsafe or of unknown water
quality without adequate disinfection before or after the System.
NO3-
NO2-
Effluent/
Percent
This system has been tested for the treatment of water containing pentavalent arsenic
Filtered
Reduction
(also known as As(V), As(+5), or arsenate) at concentrations of 0.30 mg/L or less. This
0.001
>98%
system reduces pentavalent arsenic, but may not remove other forms of arsenic. This
0.003
>97%
0.001
>99%
system is to be used on water supplies containing a detectable free chlorine residual
0.001
>99%
at the system inlet or on water supplies that have been demonstrated to contain only
0.0018
98%
0.001
>99%
pentavalent arsenic. Treatment with chloramine (combined chlorine) is not sufficient to
0.0002
99%
ensure complete conversion of trivalent arsenic to pentavalent arsenic. Please see the
0.0017
98%
0.00002
>99%
Arsenic Facts section of this Performance Data Sheet for further information.
0.001
>99%
0.001
>98%
0.0048
95%
0.001
>99%
0.0005
>99%
0.001
>99%
0.001
>99%
Arsenic Facts
0.001
>99%
0.0002
99%
Arsenic (abbreviated As) is found naturally in some
0.00059
99%
0.001
>99%
well water. Arsenic in water has no color, taste or
0.00002
>99%
odor. It is measured by a laboratory test. Public
0.0005
98%
water utilities must have their water tested for
0.0006
98%
arsenic. You can get the results from your water
0.0002
98%
0.0003
98%
utility. If you have your own well, you can have
the water tested. The local health department
0.0001
99%
0.0003
96%
or the state environmental health agency can
0.00001
>99%
provide a list of certified labs. The cost is typically
0.0002
98%
0.001
>98%
$15 to $30. Information about arsenic in water
0.000002
>99%
can be found on the internet at the U.S.
0.00001
>99%
0.0001
>99%
Environmental Protection Agency website:
0.001
>99%
0.004
>97%
epa.gov/safewater/arsenic.
0.0005
>99%
0.001
>99%
There are two forms of arsenic:
0.001
>99%
pentavalent arsenic (As(V), As(+5), and arsenate)
0.001
>99%
0.0016
99%
and trivalent arsenic (also called As(III), As(+3), and
0.001
>98%
arsenite). In well water, arsenic may be pentavalent,
0.0005
>99%
0.0046
95%
trivalent, or a combination of both. Special sampling
0.0005
>99%
procedures are needed for a lab to determine what
0.0010
>99%
Effluent/
Percent
type and how much of each type of arsenic is in the
Filtered
Reduction
water. Check with the labs in your area to see if they
0.015
95%
can provide this type of service.
Reverse Osmosis (RO) water treatment systems
0.001
>99%
do not completely remove trivalent arsenic from
water. RO systems are very effective at removing
pentavalent arsenic.
• Efficiency rating is the percentage of
the influent water to the system that is
available to the user as reverse osmosis
treated water under operating conditions
that approximate typical daily usage.
Nitrate/Nitrite Removal
This system is acceptable for treatment of influent concentration of no more than
27 mg/L nitrate and 3 mg/L nitrite in combination measured as N; and is certified
for nitrate/nitrite reduction only for water supplies with a pressure of 40 psig
(275 kPa) or greater.
A free chlorine residual will rapidly convert
trivalent arsenic to pentavalent arsenic. Other water
treatment chemicals such as ozone and potassium
permanganate will also change trivalent arsenic to
pentavalent arsenic. A combined chlorine residual
(also called chloramine) may not convert all the
trivalent arsenic. If you get your water from a public
water utility, contact the utility to find out if free
chlorine or combined chlorine is used in the water
system. The AO-US-RO-MB-6000 System is designed
to remove pentavalent arsenic. It will not convert
trivalent arsenic to pentavalent arsenic. This System
was tested in a lab. Under testing conditions, system
reduced [0.30 mg/L (ppm) or 0.050 mg/L (ppm)]
pentavalent arsenic to 0.010 mg/L (ppm) (the USEPA
standard for drinking water) or less. The perfor-
mance of system may be different with your instal-
lation. Have the treated water tested for arsenic to
check whether the system is working properly.
The RO component of the AO-US-RO-MB-6000
System must be replaced every 2 years to ensure the
system will continue to remove pentavalent arsenic.
The component identification and locations where
you can purchase the component are listed in the
installation/operation manual.
• Recovery rating is the percentage of the
influent water to the membrane portion of
the system that is available to the user as
reverse osmosis treated water when the
system is operated without a Storage Tank
or when the Storage Tank is bypassed.
NEED HELP? GIVE US A CALL 833.232.9711
SYSTEM SPECIFICATIONS
15
33
As
Arsenic

Advertisement

Chapters

Table of Contents
loading

Table of Contents