How to fix cable
Connecting with external device (optional)
All connections shall follow to the local national wiring standard.
It is strongly recommended to use manufacturer-recommended parts and accessories for installation.
For connection to main PCB
1
Two-way valve shall be spring and electronic type, refer to "Field Supply Accessories" table for details. Valve
cable shall be (3 x min 1.5 mm
sheathed cable.
* note: - Two-way Valve shall be CE marking compliance component.
- Maximum load for the valve is 9.8VA.
2
Room thermostat cable must be (4 or 3 x min 0.5 mm
similarly double insulation sheathed cable.
3
Extra pump cable shall be (2 x min 1.5 mm
4
Boiler contact cable shall be (2 x min 0.5 mm
5
External control shall be connected to 1-pole switch with min 3.0 mm contact gap. Its cable must be (2 x min
2
0.5 mm
), double insulation layer of PVC-sheathed or rubber-sheathed cable.
* note: - Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
6
Room sensor zone 1 cable shall be (2 x min 0.3 mm
sheathed.
7
Outdoor air sensor cable shall be (2 x min 0.3 mm
sheathed.
Main PCB 4
Power Supply 2
RCCB
Power Supply 1
RCCB
Indoor terminal
for connecting
cables
Holder (Clamper)
How to guide the optional cables and power supply cord
(view without internal wiring)
For connection to Optional PCB
1
By connecting Optional PCB, 2 Zone temperature control can be achieved. Please connect mixing valves,
water pumps and thermistors in zone 1 and zone 2 to each terminals in Optional PCB.
Temperature of each zone can be controlled independently by remote controller.
2
Pump zone 1 and zone 2 cable shall be (2 x min 1.5 mm
3
Solar pump cable shall be (2 x min 1.5 mm
4
Pool pump cable shall be (2 x min 1.5 mm
5
Room thermostat zone 1 and zone 2 cable shall be (4 x min 0.5 mm
heavier.
6
Mixing valve zone 1 and zone 2 cable shall be (3 x min 1.5 mm
heavier.
7
Room sensor zone 1 and zone 2 cable shall be (2 x min 0.3 mm
strength of minimum 30V) of PVC-sheathed or rubber-sheathed cable.
8
Buffer tank sensor, pool water sensor and solar sensor cable shall be (2 x min 0.3 mm
layer (with insulation strength of minimum 30V) of PVC-sheathed or rubber-sheathed cable.
9
Water sensor zone 1 and zone 2 cable shall be (2 x min 0.3 mm
or rubber-sheathed cable.
2
), of type designation 60245 IEC 57 or heavier, or similarly double insulation
2
2
), of type designation 60245 IEC 57 or heavier.
2
), of type designation 60245 IEC 57 or heavier.
2
) double insulation layer of PVC-sheathed or rubber-
2
) double insulation layer of PVC-sheathed or rubber-
Bind optional
cables with
these bands
Bind optional
cables with
these bands
2
), of type designation 60245 IEC 57 or heavier.
2
), of type designation 60245 IEC 57 or heavier.
), of type designation 60245 IEC 57 or heavier cord, or
.
rms
Optional cables:
2-way valve
cable
Room thermostat zone
1 cable
Extra pump cable
Boiler contact cable
2
), of type designation 60245 IEC 57 or heavier.
2
), of type designation 60245 IEC 57 or
2
), of type designation 60245 IEC 57 or
2
), double insulation layer (with insulation
2
), double insulation layer of PVC-sheathed
Optional cables:
External control
cable
Room sensor
zone 1
Outdoor air sensor
cable
Remote controller
cable
Power Supply 1 cord
Power Supply 2 cord
Indoor Unit/Outdoor Unit Connecting cable
2
), double insulation