Reconfirmation

Be sure to switch off all power supply before performing each
of the below checkings.

Check Water Pressure

= 1 bar)
Water pressure should not lower than 0.05 MPa (with
inspects the Water Pressure Gauge). If necessary add
water into Tank Unit (via Tube Connector g).

Check Pressure Relief Valve

Check for correct operation of Pressure Relief
Valve by turning on the lever to become
horizontal.
If you do not hear a clacking sound (due to water
drainage), contact your local authorized dealer.
Push down the lever after finish checking.
In case the water keep on draining out from the
Tank Unit, switch off the system, and then contact
your local authorized dealer.
Expansion Vessel Pre Pressure
Checking
For Space Heating / Cooling
Expansion Vessel with 10 L air capacity and initial
pressure of 1 bar is installed in this Tank Unit.
Total amount of water in system should be below
200 L. (Inner volume of Tank Unit's piping is about
5 L)
If total amount of water is over 200 L, please add
another expansion vessel. (field supply)
Please keep the installation height difference of
system water circuit within 10 m.
Check RCCB
Ensure the RCCB set to "ON" condition before check
RCCB.
Turn on the power supply to the Tank Unit.
This testing could only be done when power is
supplied to the Tank
Be careful not to touch parts other than RCCB test button
when the power is supplied to Tank Unit. Else, electrical
shock may happen.
Push the "TEST" button on the RCCB. The lever
would turn down and indicate "0", if it functions
normal.
Contact authorized dealer if the RCCB
malfunction.
Turn off the power supply to the Tank Unit.
If RCCB functions normal, set the lever to "ON"
again after testing finish.
WARNING
*(0.1 MPa
WARNING
Installation of Remote Controller as
Room Thermostat
Remote Controller mounted to the Tank Unit can
be moved to the room and serve as Room
Thermostat.
Installation Location
Install at the height of 1 to 1.5 m from the floor
(Location where average room temperature can
be detected).
Install vertically against the wall.
Avoid the following locations for installation.
1
By the window, etc. exposed to direct sunlight
or direct air.
2
In the shadow or backside of objects deviated
from the room airflow.
3
Location where condensation occurs (The
Remote Controller is not moisture proof or drip
proof.)
4
Location near heat source.
5
Uneven surface.
Keep distance of 1 m or more from the TV, radio
and PC. (Cause of fuzzy image or noise)
Remote Controller Wiring
Tank Unit
Remote Controller w
(field supply)
Terminal for Remote Controller wiring
Remote Controller cable shall be (2 x min
2
0.3 mm
), of double insulation PVC-sheathed or
rubber sheathed cable. Total cable length shall be
50 m or less.
Be careful not to connect cables to other terminals
of Tank Unit (e.g. power source wiring terminal).
Malfunction may occur.
Do not bundle together with the power source
wiring or store in the same metal tube. Operation
error may occur.
Remove The Remote Controller
From Tank Unit
Remove the top case from the bottom case.
Remote Controller
iring
No polarity
Insert the
driver and
slightly turn.
Flat-blade
screwdriver
Bottom
case
1
2