Cutting and Flaring the Piping
1
Please cut using pipe cutter and then remove the burrs.
2
Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3
Please make flare after inserting the flare nut onto the copper pipes.
Point
down
1. To cut
2. To remove burrs

Evacuation of the Equipment

WHEN INSTALLING AN AIR-TO-WATER HEAT PUMP, BE SURE TO EVACUATE THE AIR INSIDE THE UNIT
AND PIPES in the following procedure.
1
Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
Be sure to connect the end of the charging hose with the push pin to the service port.
o
2
Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and
vacuum pump adaptor.
3
Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to –76 cmHg (–0.1 MPa). Then evacuate the air approximately ten minutes.
4
Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note : BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5
Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6
Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7
Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to "OPEN"
using a hexagonal wrench (4 mm).
8
Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
o
If gauge needle does not move from 0 cmHg (0 MPa) to –76 cmHg (–0.1 MPa), in step 3 above take the following measure:
1. If the leak stops when the piping connections are tightened further, continue working from step 3.
2. If the leak does not stop when the connections are retightened, repair location of leak.
3. Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite.
Pipe
Handle
Reamer
Bar
Yoke
Core
Clamp
handle
Red arrow mark
3. To flare
Indoor unit
Vacuum
pump
adaptor
Vacuum
pump
 Improper flaring 
0 – 0.5 mm
Bar
Inclined Surface
Cracked
Copper pipe
damaged
Liquid side
Two-way valve
Close
Gas side
Three-way valve
Close
CLOSE
OPEN
CAUTION
When properly flared, the internal
surface of the flare will evenly shine
and be of even thickness. Since the
flare part comes into contact with
Uneven
the connections, carefully check
thickness
the flare finish.
Outdoor unit