Carrier 59TN6B Installation, Start-Up, Operating And Service And Maintenance Instructions page 69

Two-stage, variable-speed multipoise 35 in. (889 mm) tall, condensing gas furnace
Table of Contents

Advertisement

c. Connect a water column manometer or similar device to
manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move setup SW1- -2 on furnace control to ON position to
lock furnace in low- -heat operation. See Fig. 65 and Fig.
38.
f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on control to
start furnace. See Fig. 38.
h. Remove regulator adjustment cap from low heat gas valve
pressure regulator and turn low- -heat adjusting screw (3/16
or smaller flat- -tipped screwdriver) counterclockwise (out)
to decrease input rate or clockwise (in) to increase input
rate. See Fig. 61.
MANIFOLD PRESSURE TAP SET SCREW:
3/32" HEX HEAD ACCEPTS
INLET PRESSURE TAP
5/16" HOSE CONNECTION
SET SCREW: 3/32" HEX HEAD
ACCEPTS 5/16" HOSE
CONNECTION
1/2" NPT
INLET
ON/OFF SWITCH
Representative drawing only, some models may vary in appearance.
Fig. 61 - - Gas Valve with Tower Pressure Ports
NOTICE
DO NOT set low- -heat manifold pressure less than 1.3- -in. w.c.
(324 Pa) or more than 1.7 in. w.c. (423 Pa) for natural gas. If
required manifold pressure is outside this range, change main
burner orifices to obtain manifold pressure in this range.
i. Install low- -heat regulator adjustment cap.
j. Move setup switch SW1- -2 to OFF position after complet-
ing low- -heat adjustment.
k. Leave manometer or similar device connected and proceed
to Step 2.
2. Adjust manifold pressure to obtain high fire input rate See
Fig. 61.
a. Jumper R to W/W1 and W2 thermostat connections on fur-
nace control. This keeps furnace locked in high- -heat oper-
ation.
b. Remove regulator adjustment cap from high- -heat gas
valve pressure regulator and turn high heat adjusting screw
(3/16- -in. or smaller flat- -tipped screwdriver) counterclock-
wise (out) to decrease input rate or clockwise (in) to in-
crease input rate.
See Fig. 61.
NOTICE
DO NOT set high- -heat manifold pressure less than 3.2- -in.
w.c. (797 Pa) or more than 3.8 in. w.c. (947 Pa) for natural
gas.
If required manifold pressure is outside this range,
change main burner orifices to obtain manifold pressure in this
range.
c. When correct input is obtained, replace caps that conceal
gas valve regulator adjustment screws. Main burner flame
should be clear blue, almost transparent. See Fig. 63.
d. Remove jumpers R to W/W1 and R to W2.
REGULATOR SEAL CAP
(REGULAR ADJ. UNDER CAP)
OUTP
1/2" NPT
OUTLET
A170117
69
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
R Y W G
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
EXAMPLE: 5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
Fig. 62 - - Amp. Draw Check with Ammeter
Burner Flame
Manifold
Fig. 63 - - Burner Flame
Clocking the Meter
1. Verify natural gas input rate by clocking meter.
NOTE: Contact your HVAC distributor or gas supplier for metric
gas meter tables, if required.
a. Turn off all other gas appliances and pilots served by the
meter.
b. Move setup switch SW1- -2 to ON position. This keeps fur-
nace locked in low- -heat operation when only W/W1 is en-
ergized..
c. Jumper R to W/W1.
d. Run furnace for 3 minutes in low- -heat operation.
e. Measure time (in sec) for gas meter to complete one revolu-
tion and note reading. The 2 or 5 cubic feet dial provides
a more accurate measurement of gas flow.
f. Refer to Table 20 for cubic ft. of gas per hr.
g. Multiply gas rate cu ft./hr by heating value (Btuh/cu ft.) to
obtain input rate.
h. If clocked rate does not match required input from Step 1,
increase manifold pressure to increase input or decrease
manifold pressure to decrease input. Repeat steps b through
e of Step 1 until correct low- -heat input is achieved. Re- -in-
stall low heat regulator seal cap on gas valve.
i. Jumper R to W/W1, and W2. This keeps furnace locked
in high- -heat operation when both W/W1 and W2 are ener-
gized.
j. Repeat items d through g for high- -heat operation, repeat-
ing Step 2 and adjusting the high- -heat regulator screw as
required.
HOOK-AROUND
AMMETER
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
A96316
Burner
A11461

Advertisement

Table of Contents
loading

Table of Contents