Horizontal Or Vertical Venting - Using Single-Wall Stainless Gas Vent - Pentair MASTERTEMP MT125HD Installation And User Manual

125 pool and spa euro
Table of Contents

Advertisement

HORIZONTAL OR VERTICAL VENTING - USING SINGLE-WALL STAINLESS GAS
VENT
(SEE FIGURE 22, 23, & 24
Vent the heater either horizontally or vertically using an optional vent adapter of the 150 (6 in) or 102 mm (4 in) special
gas approved stainless steel vent pipes. Installation must be in accordance with all local codes and ordinances/or the
latest edition of the local code standards and/or local codes. The heater, when installed, must be electrically grounded
and bonded in accordance with local codes. Do not use a draft hood with this heater. Install the vent according to the
vent manufacturer's detailed instructions. Note: Keep a 150 mm (6 in) minimum clearance between the vent pipe and
combustible surfaces. Follow the vent manufacturer's instructions and code requirements. Do not place any insulating
materials around the vent or inside the required clear air space surrounding the vent. See Table 5 for maximum permissible
vent lengths.
The allowable vent runs for each vent pipe diameter are different and can not be exceeded.
Each 90-degree elbow reduces the maximum horizontal vent run by 3.6 m (12 feet) and each 45-degree
elbow in the vent run reduces the maximum vent run by 1.8 m (6 feet). See Table 5 for the maximum vent
lengths using 90° elbows.
152 mm (6 in.) or 102 mm (4 in)
Special Gas Vent (Vertical or Horizontal)*
No. of 90° El-
bows
0
1
Table 5. (*) Minimum vent length is 305 mm (1 ft.) or in accordance with vent manufacturer's instruction, and local
and national codes. Horizontal vents 1 m (3 ft) or less in length do not require a condensate tee, but must slope down
toward the outlet at 2 cm to the meter (1/4 in / ft.) to allow condensate to drain.
It is recommended that vent runs over 5.4 m (18 feet) may need to be insulated to reduce condensation related
problems and/or the use of a condensate trap in the vent run close to the heater may be necessary in certain
installations such as cold climates. Horizontal vents 1 m (3 ft) or less in length do not require a condensate tee.
The MasterTemp heater is suitable for through-the-wall venting.
Flue gases may escape into the dwelling with any cracks or loose joints in the vent pipe, or improper vent installation.
The vent pipe must be of a sealed-seam construction and for operating temperatures less than 204° C (400°F). Vent
pipe construction will be according to local code standards, approved non-corrosive material, such as stainless steel. A
condensate trap may be needed. The use of "Approved" thimbles, roof jacks and/or side vent terminals are required; and
the proper clearances to combustible materials must be maintained in accordance with type of vent pipe employed—in
the absence of a clearance recommendation by the vent pipe manufacturer, the requirements of the Uniform Mechanical
Code should be met. The ventilation air requirements for the MasterTemp heater can be found on page 18. It is
recommended that vent runs over 5.4 M (18 ft) may need to be insulated to reduce condensation related problems and/
or the use of a condensate trap in the vent run close to the heater may be necessary in certain installations such as cold
climates. Horizontal vents 1 M (3 ft) or less in length do not require a condensate tee. The MasterTemp heater is suitable
for through-the-wall venting.
NOTE:
After installation, installer must check for correct and safe operation of the heater.
)
ON PAGE 19
NOTE
Maximum Length in Feet (M)
11.6 m (38 ft.)
8 m (26 ft.)
NOTE
MasterTemp 125 Pool and Spa Heater Installation and User's Guide
Section 2. Installation
17
|

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mastertemp mt125461078461079460902460903

Table of Contents