NSTALLATION AND PERATION ANUAL ClimaticControl-HC Heating & Cooling Controller IMPORTANT! Before starting work the installer should carefully read this Installation & Operation Manual, and make sure all in- structions contained therein are understood and observed. ClimaticControl-HC should be mounted, operated and maintained by specially trained personnel only. Personnel in the course of training are only allowed to handle the product under the supervision of an experienced fitter.
1. Application ClimaticControl-HC is developed for variable flow temperature control in heating and cooling systems particular in low-temperature installations like floor heating and cooling systems. The flow temperature is controlled de- pending of the outside temperature following a curve. Using the ClimaticControl-HC the operation of a water floor system can be adapted to the actual demands of the ...
4. Display Operating modes Keyboard is locked Service Installation Menu Manual operation / program override active (display of temperature offset) a) display temperature (°C / °F) b) display time (12 h / 24 h) Type of temperature displayed Water temperature Outside temperature Room temperature (if RF room thermostat con- nected)
ARA 600 3-Point actuator 3 point actuator Standard Black installation according to WATTS installation 3-ways mixing valve Blue installation. EVO2 Brown (See hydraulic modul or...
Hydraulic installation The configuration is defined by the System parameter #4: INST (See Chap 7.1 System parameters setting) and induces a different usage of the ouputs: Pump2/Cooling ouput : Paramter #4 INST 2P.1 or 2P.2 Output Directive valve Cooling demand Pump 2 Heating ouput : Paramter #4 INST...
Page 7
5.3.2 Single circuit hydraulic installation: Parameter #4=SEP Security Contact thermostat Optionnal Return sensor (Used when no RF thermostat is installed) Supply water sensor Main pump Mixing 3 way valve Boiler control Water chillers signal Heating Mode Cooling mode Heating demand output driving the boiler or Active (Contact closed) when the pump 1 is Always OFF (Contact opened) Stage 2 heating (if PE=yes)
Page 8
5.3.4 Dual circuit hydraulic installation: Parameter #4=2P.1 or 2P.2 with RF thermostat: 2P.1 or 2P.2 with RF thermostats have the same behavior: In cooling mode, the climatic control will automatically reverse the cooling demand if the thermostat 2 is not reversible 2P.1 or 2P.2 with RF thermostat Heating Mode Cooling mode...
Room Temperature – Direct Plug In As an option you can plug in a room thermostat to the ClimaticControl-HC. Direct plug in of a room thermostat op- timizes the operational time of the circulation pump and even the supply flow temperature depending on the condi- tions in the main room.
Page 10
5.4.3 Wireless room thermostat (Water Floor thermostat “trF1”) with WFHT-RF (BASIC, LCD or MILUX) MILUX-RF-Hygrostat MILUX-RF-xxx WFHT-RF BASIC WFHT-RF LCD Only RF thermostats from the WFHT-RF series or the MILUX-RF series can be used with an active antenna 433,92. The MILUX-RF Hygrostat can be used only with the 433,92Mhz frequency RF thermostat initialization to the Controller: SYSTEM PARAMETERS MENU, section ...
Page 11
5.4.6 Wireless RF outside sensor (Inst: System parameters: Input, “OUSE”). As an option you can plug in a wireless RF outside sensor room thermostat to the ClimaticControl-HC. This solu- tion is very interesting in rehabilitation, to avoid wires trough the wall, in a building management with several CC- HC, in this case only one outside sensor can be installed to manage all the building.
Page 12
Inst: System parameters: Input, “C_b” In case of mutizone regulation “WFHC Master RF with or without Heat&Cool function” is installed you could use the input 1 to connect the pump relay output to swtich off the circulation pump1 in case of no water circulation demand is asked in the house.
Page 13
Example 2: Under floor heating installation with multizones connecting boxes. In1 used to stop the pump when no heat demand is asked in the house. (Inst: Parameters menu: In1, “C_b”) In2 used to stop the pump when the storage tank is empty (Inst: Parameters menu: In2, “Aqu”) WFHC Pump signal closed = pump On...
6. Types of operating modes / Program menu 6.1 Heating and cooling switch There are several ways to switch the system between heating and cooling. Use parameter #0 Type (See Chap 7.1) Use the user interface of the Climatic Control HC if parameter #0 Type=Rev (See Chap 7.1) ...
Page 15
AUTOMATIC mode of operation Automatic mode of operation using the built-in or user programs. The ClimaticControl-HC is controlled according to the selected built-in or user program ( 6.2.). The flow temperature is controlled depending on the outdoor temperature and the curve with room com- pensation if RF thermostat is installed.
STOP mode This mode is used to switch off the system. The device switches off the system. The ClimaticControl-HC software version is indicated on the display for about 3 seconds and then switches off (no indications). By pressing any of the keys the ClimaticControl-HC can be switched on. REMARK: When the ClimaticControl-HC is in STOP mode, In Heating mode only an Anti-freeze function can restart heat relay and circulation pump to maintain the water temperature above 10°C.
Page 17
Day of the week Cursor time The key (+) allow you to choose a COMFORT period at the blinking cursor time. The key (+) allow you to choose a REDUCED period at the blinking cursor time. At 13 the time indication blinks and day 1 is highlighted, while at 7 the time cursor blinks at 0 h on the sym- bol (heating mode).
The ClimaticControl-HC program operates only in mode according to the selected COMFORT and REDUCED temperature periods. 7 System Parameter Menu 7.1 System parameters setting This menu is used to set the most important parameters for the operation of the system. To access this menu keep the (OK) key pressed for 10 seconds (in Comfort, Auto, Reduced modes).
Page 19
SYSTEM PARAMETERS Factory Alternative Values Parameters description setting setting setting _ _ _ Type Type of installation Following your choice, the list of parameter will be different. Ex: The Cooling “curve” parameter will be not displayed if you choose “Hot” installation.
Page 20
2P.1: Panel Heaters + water floor 2P.1 heating and cooling system The second pump for direct temperature circuit (panel heater) will be stopped in cooling mode. No cold water in panel heater! 2P.2: Fan coil units and Water Floor 2P.2 Heating and Cooling system The second pump is used to control a fan...
Page 21
Selecting „no thrF“ disconnects the RF thermostat from the Controller and discontinues the room temperature plug-in function respectively. Connection of wireless room thermostat is only possible using appropriate device. The following parameter is only available if “th” parameter is set to “rF” and if “inst”...
Page 22
Aqu: A water Aquastat is wired on Input2. If over temperature is reached (contact open) then: - if “inst”=”Act or SEP”, Pump1 circulation is stopped & mixing valve is closed. - if “inst”=”2P.x”, direct circuit Pump2 circula tion is stopped The HC signal could be done by a heat pump.
Page 23
If PE = No Conventional operation of the free contact "Heating output" (See Chap 5.3) If PE = Yes See below explanations on “PE t” ------------- Setting the desired PE outdoor temperature. PE t If PE = Yes -7°C (Efficiency Point •...
Reset function By keeping the (OK) key pressed for about 5 seconds all system parameters, time and day of the week as well as user programs in are reset to the factory setting. Established radio configuration to rf thermostats, if any, is also erased. The cursor moves to Press on the (OK) key to exit the installer menu and come back to the main menu in mode.
Outputs: pump: 5 A / 250 V relay (L, N, PE) Cold: 5 A / 250 V relay (L, N, PE) Heat: 5 A / 250 V relay (Free contact) 3-point control: 2 TRIACS => 75 W max. "Maximum opening time 240 seconds; Suitable for actuators that have an opening time below 240 Seconds”...