7.8. Earthing
Earth the fixed version circuit-breaker by means of the special
screw marked with the relative symbol.
Clean and degrease the area around the screw to a diameter
of about 30 mm and, on completion of assembly, cover the
joint again with Vaseline grease.
Use a conductor (busbar or braid) with a cross section
conforming to the Standards in force.

7.9. Connection of the auxiliary circuits

Note: the minimum cross section of the wires used for the
auxiliary circuits must not be less than the one used for the
internal wiring. Furthermore, they must be insulated for 3 kV
test voltage.
7.9.1. Socket wiring Kit
The eVD4 socket wiring kit allows simple and rapid
construction of the panel wiring part. It consists of:
– 58-pin socket pre-engineered for Ethernet electric ports (1)
– Cables 1.5 metres long with 2.5 mm
cables for the power connections and with 1 mm
section for the signal connections
– Serial cable 1.5 m long for the signal connection with the
HMI fitted with special connector on the end (2)
– 2 Ethernet connection modules 1.5 m long with cylindrical
connector on the socket side and RJ45 connector on
the other end. Allows easy integration of the eVD4 in
communication systems based on Ethernet (3)
3
Fig. 10
50
50
cross section copper
2
cross
2
1
2
7.9.2. Withdrawable and fixed circuit-breaker
The auxiliary circuits of the withdrawable and fixed circuit-
breaker are fully factory-wired up to the connector (fig. 11).
For external connections, refer to the electric wiring diagram
of the switchgear.
eVD4 circuit-breaker for UniGear switchgear and PowerCube units.
Fig. 11