5.5.3. Types of withdrawable circuit-breakers available for PowerCube units
eVD4/P withdrawable circuit-breakers (12 kV)
Circuit-breaker
Standards
VDE 0671; CEI EN 62271-100 file 7642 •
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated thermal current (40 °C) (
1
Rated breaking capacity
(symmetrical rated short-
circuit current)
Short-time withstand
current (3s)
Making capacity
Sequence of operations
Opening time
Arcing time
Total breaking time
Closing time
P P
Maximum
overall
H
dimensions
D
W
Weight
Standardized dimensions table
Operating temperature
Tropicalization
Electromagnetic compatibility
(1) Rated current guaranteed when circuit-breaker is installed in a PowerCube enclosure and with 40 °C ambient temperature
(2) For lower temperature please ask ABB.
38
38
PowerCube unit PB1
IEC 62271-100 •
Ur [kV] 12
Us [kV] 12
Ud (1 min) [kV] 42
Up [kV] 75
fr [Hz] 50-60
)
Isc [kA]
Ik [kA]
Ip [kA]
[O - 0.3 s - CO - 15 s - CO] •
H [mm] 621
W [mm] 503
D [mm] 662
Pole centre-distance P [mm] 150
1VCD 000163
IEC: 60068-2-30, 60721-2-1 •
IEC: 62271-1 •
eVD4/P 12
PB2
12
12
42
75
50-60
Ir [A] 630
1250
1250
16
16
20
20
25
25
31.5
31.5
40
16
16
20
20
25
25
31.5
31.5
40
40
40
50
50
63
63
80
80
100
[ms] 33 ... 60
33 ... 60
[ms] 10 ... 15
10 ... 15
[ms] 43 ... 75
43 ... 75
[ms] 60 ... 80
60 ... 80
621
691
503
653
662
641
150
210
[kg] 116
116
174
000163
000166
[°C] - 5 ... + 40 (
)
- 5 ... + 40 (
2
1600
1600
2000
20
20
25
25
31.5
31.5
40
40
20
20
25
25
31.5
31.5
40
40
50
50
63
63
80
80
100
100
691
691
691
653
653
653
640
641
640
210
210
210
160
174
160
000164
000166
000164
)
2
PB3
12
12
42
75
50-60
2500
20
25
31.5
40
20
25
31.5
40
50
63
80
100
33 ... 60
10 ... 15
43 ... 75
60 ... 80
691
853
640
275
221
000175
- 5 ... + 40 (
)
2