3.35 Separator condition –
The value given at this function is the efficiency rating of the dust separator element in
the detector as a percentage of the efficiency of a clean separator. A new element will
give a reading of 99 in this function. When the efficiency has decreased to 80%, the
Fault indicator LED will illuminate and the event log will show "Separator renew".
Note - After fitting a new element, it will be necessary to start a FastLearn to reset the
separator condition reading (see section 3.7).
3.36 Separator change date –
This function defaults to "--", which means that a separator fault will only appear
when the efficiency decreases to 80% (see 3.35, "Separator condition"). However, a
date may be entered into this function to allow for a scheduled maintenance period.
The detector will then generate a separator fault at the planned time regardless of the
condition of the separator, although degradation of the separator to below 80% effi-
ciency before this date will override this.
See section 10, "Maintenance" for further details.
3.37
Factory default –
Enabling this function will reset each programmable function to the default value indi-
cated in the text, where a default setting is specified. It will also put the detector into
FastLearn mode, regardless of whether or not Auto Fastlearn is enabled (see section
3.8). This ensures that the flow setups and alarm thresholds are optimised to the detec-
tor's working environment after resetting. It should be noted that where a ClassiFire
alarm factor other than the default is required for the protected area, this will need to
be re-entered. Section 3.5 gives details of the ClassiFire alarm factors.
4.1 Reset
If latching alarms (see section 3.15) or latching faults (see section 3.16) are enabled,
the relevant alarm or fault warnings will remain on the detector front panel LEDs and
controlling unit until a reset is performed. If using SenseNET software, individual detec-
tors can be reset (refer to the SenseNET User Guide for details). In the remote software,
a global reset is available which resets all detectors on the SenseNET loop, or a single
stand-alone detector.
To perform a reset, either select the menu options "Options ' Global Reset" or click
the symbol indicated below.
Stratos-Micra • INSTALLER'S HANDBOOK • Iss. 16
www.acornfiresecurity.com
tab
Miscellaneous
tab
Miscellaneous
tab
Miscellaneous
Page 15