[ IX Troubleshooting ]

5. Trouble criterion of main parts

Part name
Room temperature

thermistor

(TH1)
Pipe temperature
thermistor/liquid
(TH2)
Condenser/evaporator
temperature thermistor
(TH5)
6. Thermistor
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Thermistor R
=15kΩ ± 3%
0
Fixed number of B=3480kΩ ± 2%
Rt=15exp { 3480(
0°C
15kΩ
10°C
9.6kΩ
20°C
6.3kΩ
25°C
5.2kΩ
30°C
4.3kΩ
40°C
3.0kΩ
HWE20020
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Normal
4.3kΩ~9.6kΩ
Room temperature thermistor (TH1)
Pipe temperature thermistor (TH2)
Condenser/evaporator temperature
thermistor (TH5)
1
1
) }
273+t
273
Check method and criterion
Abnormal
Opened or short-circuited
- 34 -
< Thermistor for lower temperature >
50
40
30
20
10
0
-20 -10 0
10 20 30 40 50
Temperature (°C)
GB