Table 11 - Routine Maintenance Plan For Critical Application And/Or Highly Aggressive Environment - Daikin EWAT016CZN-A1 Installation, Maintenance And Operation Manual

Air to water heat pump units with scroll compressors
Table of Contents

Advertisement

List of Activities (Note 8)
General:
Reading of operating data (Note 3)
Visual inspection of unit for any damage and/or loosening
Verification of thermal insulation integrity
Cleaning
Paint where necessary
Analysis of water (4)
Check of flow switch operation
Electrical Installation:
Verification of control sequence
Verify contactor wear – Replace if necessary
Verify that all electrical terminals are tight – Tighten if necessary
Clean inside the electrical control board
Visual inspection of components for any signs of overheating
Verify operation of compressor and electrical resistance
Measure compressor motor insulation
Refrigeration circuit:
Check for any refrigerant leakage (leak test)
Analyze compressor vibrations
Hydraulic circuit:
Check for any water leakage
Check hydraulic connections
Check the pressure at the pump inlet
Clean the water filter
Check the glycol concentration
Check the water flow rate
Check the safety valve
Coil section:
Checking the cleaning of the air heat exchanger (Note 6)
Check the cleaning of water heat exchangers (Note 6)
Verify that fans are well tightened
Verify coil fins
BPHE:
Check the cleaning of the BPHE
Table 11 – Routine Maintenance Plan for Critical Application and/or Highly Aggressive Environment
Notes:
7. Monthly activities include all the weekly ones.
8. The annual (or early season) activities include all weekly and monthly activities.
9. Daily reading of the operating values of the unit allows maintaining high observational standards.
10. Check for any dissolved metals.
11. Clean condenser banks with clean water and water heat exchangers with appropriate chemicals. Particles and fibers could clog up the exchangers, especially for
water exchangers pay attention if water rich in calcium carbonate is used. An increase in pressure drops or a decrease in thermal efficiency means that the heat
exchangers are clogged. In environments with a high concentration of airborne particles, it might be necessary to clean the condenser bank more often.
12. Units placed or stored in a Highly Aggressive Environment for long time without operation are still subject to those routine maintenance steps.
EWYT~CZ / EWAT~CZ
Monthly
Weekly
(Note 1)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
DEIMHP0140521_00EN
Yearly/Seasonal
(Note 2)
X
X
X
X
X
X
X
X
X
X
X
X
X
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents