To start a manual defrost
1. Push the DEF key for more than 3 seconds and a manual defrost will start.
How to lock the keyboard
1. Kee
and
the keyboard is unlocked..
2. The "POF" message will be displayed and the keyboard is locked. At this point it is only possible the
viewing of the set point or the MAX o Min temperature stored and to switch ON and OFF the light, the
auxiliary output and the instrument.
To unlock the keyboard
Keep the
and
ON/OFF function
By pushing the ON/OFF key, the instrument shows "OFF" for 5 sec. and the ON/OFF LED is switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped;
N.B. During the OFF status the LED4 button is lighted.
10.

WIRING

A wiring diagram, specific for the units of the LMSW series, is enclosed with these use and
maintenance instructions.
11.

MAINTENANCE AND REPAIRS

Suitable maintenance is crucial for obtaining longer life, perfect working conditions and
efficiency of the unit as well as for ensuring the safety features provided by the manufacturer.
12

ROUTINE MAINTENANCE

Good operation of the unit requires the condenser to be cleaned periodically (frequency of cleaning
depends on the environment where the unit is installed).
Turn off the unit and clean it by blowing air from the inside outwards. Should no air jet be
available, use a long-haired brush and work on the outside of the condenser.
In case of water-cooled condensers have the unit cleaned by a plumber with special descaling
agents.
WARNING
Use safety gloves to protect your hands from possible cuts.
WARNING
Disconnect the unit before working on it.
12.2

Periodical maintenance

Periodically check wear condition of electrical contacts and remote switches; if necessary replace
them.

12.2 Service operations to be carried out by qualified technicians or by the manufacturer

Following operations shall be carried out by qualified technicians or by the manufacturer exclusively.
Under no circumstances the user is allowed to:
 replace electrical components
 work on the electric equipment
 repair mechanical parts
 work on the refrigerating system
 work on the control panel, ON/OFF and emergency switches
 work on protection and safety devices.
keys pressed together for more than 3 the "POn" message will be displayed and
keys pressed together for more than 3s.
high