Rexroth IndraDrive Drive Controllers Power Sections HMS02
Control Voltage or Auxiliary Voltage
Connection
Line Routing
6.2.6
Design and Installation in Area C - Strongly Interference-Susceptible
Area of Control Cabinet
Influence of the Motor Power Cable
Routing the Motor Power Cables
and Motor Encoder Cables
Routing the Motor Power Cables
and Mains Connection Lines
Alternative: Shield modules, components and lines in area B by distance plates
mounted vertically on the mounting plate from modules and lines in area A or
use shielded lines.
Only connect power supply units for auxiliary or control voltage connections in
the drive system to the mains via a mains filter. See
(Zones), page
46.
Install the shortest possible lines between drive controller and filter.
Only in exceptional cases should you connect power supply unit and fusing for
the control voltage connection to phase and neutral conductor. In this case,
mount and install these components in area A far away from the areas B and
C of the drive system. For details see section
Area A - Interference-Free Area of Control Cabinet, page
Run the connection between control voltage connection of the drive system and
power supply unit used through area B over the shortest distance.
Run the lines along grounded metal surfaces, in order to minimize radiation of
interference fields to area A (transmitting antenna effect).
Area C mainly concerns the motor power cables, especially at the connection
point at the drive controller.
The longer the motor power cable, the greater its leakage capacitance. To
comply with a certain EMC limit value, the allowed leakage capacitance of the
mains filter is limited. For the calculation of the leakage capacitance, see the
documentation on the drive system of the drive controller used.
Run the shortest possible motor power cables.
Only use shielded motor power cables by Rexroth.
Route the motor power cables and motor encoder cables along grounded metal
surfaces, both inside the control cabinet and outside of it, in order to minimize
radiation of interference fields. If possible, route the motor power cables and
motor encoder cables in metal-grounded cable ducts.
Route the motor power cables and motor encoder cables
with a distance of at least d5 = 100 mm to interference-free lines, as well
as to signal cables and signal lines
(alternatively separated by a grounded distance plate)
in separate cable ducts, if possible
For converters (drive controllers with individual mains connection), route motor
power cables and (unfiltered) mains connection lines in parallel for a maximum
distance of 300 mm. After that distance, route motor power cables and power
supply cables in opposite directions and preferably in separate cable ducts.
Ideally, the outlet of the motor power cables at the control cabinet should be
provided in a distance of at least d3 = 200 mm from the (filtered) power supply
cable.
Bosch Rexroth AG
EMC Measures for Design and Installation
6.2.2 Division Into Areas