E: 64. Pfc Circuit Error (Outdoor Unit) - Fujitsu ACUH09LUAS1 Service Manual

Hide thumbs Also See for ACUH09LUAS1:
Table of Contents

Advertisement

2-19. E: 64. PFC circuit error (Outdoor unit)

→ired remote
Indicator
controller
Detective actuator
Outdoor unit
Forecast of cause
Check point 1. Check external cause at indoor and outdoor (Voltage drop or Noise)
Instant drop: Check if there is a large load electric apparatus in the same circuit.
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check point 2. Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
Check point 3. Replace main PCB
If check point 1 to 2 do not improve the symptom, change main PCB.
2-19. E: 64. PFC circuit error (Outdoor unit)
Error code
Main PCB
End
→hen inverter input DC voltage is higher than 415
V for over 3 seconds, the compressor stops.
If the same operation is repeated 5 times, the
compressor stops permanently.
External cause
Connector connection failure
Main PCB failure
- (03-23) -
E: 64
2. Troubleshooting with error code