Compressor Frequency At Normal Start-Up - Fujitsu ACUH09LUAS1 Service Manual

Hide thumbs Also See for ACUH09LUAS1:
Table of Contents

Advertisement

1-4. Compressor frequency at normal start-up

¢ Model: AOUH09LUAS1
Compressor frequency soon after starting is controlled as below.
Frequency VII
Frequency VI
Frequency V
Frequency IV
Frequency III
Frequency II
Frequency I
Frequency (rps)
Time (sec)
¢ Models: AOUH12LUAS1 and AOUH18LUAS1
Compressor frequency soon after starting is controlled as below.
Frequency VI
Frequency V
Frequency IV
Frequency III
Frequency II
Frequency I
Frequency
(rps)
Time (sec)
1-4. Compressor frequency at normal start-up
Time 1
Time 2
I
II
45
56
1
2
60
140
Time 1
Time 2
I
II
35
52
1
2
60
140
Time 3
Time 4
Time 5
III
IV
68
77
3
4
170
220
Time 3
Time 4
III
IV
64
71
3
4
170
200
- (04-5) -
Time 6
Time 7
V
VI
84
93
5
6
280
360
Time 5
Time 6
V
VI
89
97
5
6
350
410
1. Compressor frequency control
VII
103
7
430