Installation Guide
Electronic controller
MCX08M2 with TTL
ANALOG INPUTS
NTC, 0/1 V, 0/5 V, 0/10 V, PT1000, selectable via software
Universal NTC, Pt1000, 0/1 V, 0/5 V, 0/10 V, ON/OFF, 0/20 mA, 4/20 mA, selectable via software
Total number
DIGITAL INPUTS
Voltage free contact
Total number
ANALOG OUTPUTS
0/10 V DC optoinsulated
0/10 V DC, PWM, PPM selectable via software
Total number
DIGITAL OUTPUTS
SPST relay 16 A (normally open contacts)
SPST relay 8 A (normally open contacts)
SPDT relay 8 A (changeover contacts)
Total number
OTHERS
Power supply 110 V / 230 V AC
Connection for programming key
Connection for remote display and keyboard
Buzzer
CANbus
RTC clock
Modbus RS485 serial interface
Serial TTL
Dimensions (DIN modules)
Mounting
© Danfoss | DCS (vt) | 2021.01
General features:
MCX08M2 is an electronic controller that holds all the typical functionalities of MCX controllers
in the compact size of 8 DIN modules: programmability, connection to the CANbus local
network, Modbus RS485 serial communication interface.
MCX08M2 with TTL version is moreover available in the version with display and power supply
110 – 230 V AC.
080R9348
AN358818754869en-000201
MCX08M2 with TTL
4
4
8
8
8
2
2
4
2
2
4
8
8
DIN rail
AN358818754869en-000201 | 1

Advertisement

loading

Summary of Contents for Danfoss MCX08M2

  • Page 1 8 DIN modules: programmability, connection to the CANbus local network, Modbus RS485 serial communication interface. MCX08M2 with TTL version is moreover available in the version with display and power supply 110 – 230 V AC.
  • Page 2 Disposal instruction Equipment containing electrical components may not be disposed together with domestic waste. It must be separately collected with electrical and electronic waste according to local and valid legislation. 2 | AN358818754869en-000201 © Danfoss | DCS (vt) | 2021.01...
  • Page 3: Technical Specifications

    Characteristics of each relay: • 6 A 250 V AC for resistive loads - 100.000 cycles • 4 A 250 V AC for inductive loads - 100.000 cycles with cos(phi) = 0.6 © Danfoss | DCS (vt) | 2021.01 AN358818754869en-000201 | 3...
  • Page 4: Connection Diagram

    (100 mA max) only for 080G0335 NTC, 0/1 V, 0/5 V, 0/10 V, PT1000 BOTTOM BOARD To the AI (120 mA max) max) 0G0335 NTC, 0/1 V, 0/5 V, 0/10 V, PT1000 4 | AN358818754869en-000201 © Danfoss | DCS (vt) | 2021.01...
  • Page 5: User Interface

    Enter and X key after power ON to access the BIOS menu and select the DISPLAY menu. Use UP and DOWN arrow keys to adjust the contrast or the brightness of the display at the desired level. Dimensions LCD Display No Display © Danfoss | DCS (vt) | 2021.01 AN358818754869en-000201 | 5...
  • Page 6: Product Part Numbers

    Product part numbers Description Code No. MCX08M2, 230 V, LCD, RS485, TTL, Single Pack 080G0335 Accessories part numbers Description Code No. MCX08M CONNECTORS KIT 080G0180 6 | AN358818754869en-000201 © Danfoss | DCS (vt) | 2021.01...

This manual is also suitable for:

080g0335