To Put A Zone In And Out Of Test Mode - Gent 800 Operator's Manual & Log Book

Fire alarm panel
Hide thumbs Also See for 800:
Table of Contents

Advertisement

To put a zone in and
out of test mode
A2
Select
P ress select to c ha nge to a re qu ired
zone nu m b er
Previous
P ress to select In Te st fie ld [ ]
26
796689 (4188-658) _ I1.1 /02.01
Any zone can be individually put into test
mode to allow the devices in the zone to be
tested. In test mode the panel will not detect
fires from devices in the zone of the
protected building. An active manual call
point or detector in the zone will cause
master alarms to sound for a short duration
and the device is reset thereafter. On
completion of the test it is important to exit
the zone from test mode to resume normal
operation.
Y
Enter access level 2 (A2) and use the
navigation buttons to highlight and
select options:
Next
Select
P ress select to togg le NO/YES
Select NO to take zone out of test
or YES to put the zone in test
Previous
Next
P ress to select a zon e field [ ]
Test