FCAG35~140BVEB
Split system air conditioners
4P561448-1B – 2021.07
a
a Centre of the unit
b Centre of the ceiling opening
c Paper pattern for installation (upper part of the packing)
d Screws (accessories)
Ceiling opening and unit:
-
Make sure the ceiling opening is within the following limits:
Minimum: 860 mm to be able to fit the unit.
Maximum: 910 mm to ensure enough overlap between the decoration panel
and the suspended ceiling. If the ceiling opening is larger, add extra ceiling
material.
-
Make sure the unit and its hanger brackets (suspension) are centered within
the ceiling opening.
a
b
c
d
e
f
a Drain piping
b Refrigerant piping
c Hanger bracket pitch (suspension)
d Unit
e Ceiling opening
f Decoration panel
Example
A
B
C
(a)
A: Ceiling opening
B: Distance between the unit and the ceiling opening
C: Overlap between the decoration panel and the suspended ceiling
Installation guide. Use the installation guide to determine the correct vertical
position.
b
c
d
710
840
860~910
950
(mm)
If A
860 mm
910 mm
6
Installation
|
(a)
Then
(a)
B
10 mm
35 mm
Installer and user reference guide
(a)
C
45 mm
20 mm