System Layout; Combining Units And Options; Possible Options For The Indoor Unit; Possible Combinations Of Indoor Unit And Outdoor Unit - Daikin FCAHG71FVEB Installer And User Reference Manual

Split system air conditioners
Hide thumbs Also See for FCAHG71FVEB:
Table of Contents

Advertisement

5 Preparation

(a)
To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions,
safety devices may be put in action and the air conditioner
may not operate.
4.4

System layout

NOTICE
Design of the system must not be done at temperatures
below –15°C.
f g
a
i
e
d
c
a
Indoor unit
b
Outdoor unit
c
User interface
d
Suction air
e
Discharge air
f
Refrigerant piping + interconnection cable
g
Drain pipe
h
Earth wiring
i
Suction grille and air filter
4.5

Combining units and options

4.5.1

Possible options for the indoor unit

Make sure you have the following mandatory options:
▪ User interface: Wired or wireless
▪ Decoration panel: Standard or self-cleaning
4.5.2
Possible combinations of indoor unit and
outdoor unit
Indoor unit
RZAG71
FCAHG71
O
FCAHG100
FCAHG125
FCAHG140
5
Preparation
5.1

Overview: Preparation

This chapter describes what you have to do and know before going
on-site.
It contains information about:
▪ Preparing the installation site
Installer and user reference guide
8
b
h
Outdoor unit
RZAG100 RZAG125 RZAG140
O
O
O
▪ Preparing the refrigerant piping
▪ Preparing the electrical wiring
5.2

Preparing installation site

Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit must be covered.
Choose the installation location with sufficient place for carrying the
unit in and out of the site.
5.2.1
Installation site requirements of the
indoor unit
INFORMATION
Also read the following requirements:
▪ General
installation
"General safety precautions" chapter.
▪ Refrigerant
piping
difference). See further in this "Preparation" chapter.
INFORMATION
The sound pressure level is less than 70 dBA.
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation
in
a
commercial
environment.
NOTICE
The equipment described in this manual may cause
electronic noise generated from radio-frequency energy.
The equipment complies to specifications that are
designed to provide reasonable protection against such
interference. However, there is no guarantee that
interference will not occur in a particular installation.
It is therefore recommended to install the equipment and
electric wires keeping proper distances away from stereo
equipment, personal computers, etc.
f
e
d
a
Earth leakage protector
b
Fuse
c
Outdoor unit
d
Indoor unit
e
User interface
f
Personal computer or radio
In places with weak reception, keep distances of 3  m or more to
avoid electromagnetic disturbance of other equipment and use
conduit tubes for power and transmission lines.
▪ Fluorescent lights. When installing a wireless user interface in a
room with fluorescent lights, mind the following to avoid
interference:
▪ Install the wireless user interface as close as possible to the
indoor unit.
▪ Install the indoor unit as far as possible from the fluorescent
lights.
site
requirements.
See
the
requirements
(length,
height
and
light
industrial
a
b
c
(mm)
FCAHG71~140FVEB
Split system air conditioners
4P429475-1 – 2015.12