Increased DTU binding and remote monitoring function 2011-08-21 Increase the panel can set parameters of the items 2013-06-06 LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. Page 1 of 36 �: T:+86-769-23836636 �: F:+86-769-23166296 � : : : : www.lixise.com...
8. During "start idle delay", under speed, under frequency, under voltage alarms are inhibited. When this delay is over, "warming up delay" starts (if configured). LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 6 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
After generator runs well, if remote start signal is active, controller will send closing gens signal; if the remote signal is inactive, controller won′t send closing signal. LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 7 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
1:Mains load is transferred into generator load, after the delay of switch off and transfer interval, generator LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 8 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Recorded Recorded data data data data display display display display window window window window LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 14 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Key can immediately interrupt the current setting of parameters, and returns the operation of standby. LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 19 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Mains closing and gen closing pulse width Closing pulse time (0-5s) of 0 means continuous output. LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 20 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Page 21
When an external pressure sensor value (1-399)kPa ( warning ) is less than this value, the delay start oil LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 21 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Page 22
Output 5 way (0-1) 1:Normally closed output Output 6 function (0-87) 14: Open Mains selection LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 22 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Start Relay Action when genset is starting and disconnect when start is completed. LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 24 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Page 25
Action when generator under frequency warning. warning Gen under frequent Action when generator under frequency shutdown. shutdown LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 25 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Page 26
Under speed This output indicates that an under speed shutdown has occurred. Shutdown LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 26 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
When activated, the panel will display an alarm. Over Current Trip When active, the panel displays an overcurrent alarm input. LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 28 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
ATS’ wires connection of control part according to this manual. 9. If there is any other question, please contact Feirui’s service. LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. � Page 31 of 36 �: T:+86 0769-23162896 �: F:+86 0769-23166296 : : : : www.lixise.com...
Page 35
Note:a.ICOM port must be connected to negative pole of battery controller power.b.When there is load current, transformer’s secondary side prohibit from open circuit. LXC63X0/LXC51X0 Generator controller user manual. Dongguan Tuancheng Automation Equipment Co.,LTD. Page 35 of 36 � �: T:+86-769-23836636 �: F:+86-769-23166296 : : : : www.lixise.com...