LIXiSE LXC706 Series User Manual

LIXiSE LXC706 Series User Manual

Genset controller

Advertisement

LXC706
Genset Controller User Manual
Ver1.1
Date: 2014/03/20
Software version
Date
2013-05-10
2014-03-20
LXC706 Product User Manual
: +86-769-23836636
LXC706 SERIES
Versio
Note
n
1.0
Original release.
1.1
Added USB interface for directly connecting to PC.
: F:+86-769-23166296
LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
Dongguan Tuancheng Automation Equipment Co.,Ltd.
: www.lixise.com
Page 1 of 17

Advertisement

Table of Contents
loading

Summary of Contents for LIXiSE LXC706 Series

  • Page 1 LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. LXC706 Genset Controller User Manual Ver1.1 Date: 2014/03/20 LXC706 SERIES Software version Date Versio Note 2013-05-10 Original release. 2014-03-20 Added USB interface for directly connecting to PC. LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
  • Page 2: Table Of Contents

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. ontents 1. SUMMARY..................................3 2. FEATURES..................................3 3. PERFORMANCE................................3 4. SPECIFICATION................................4 5. DISPLAY SYMBOL AMD OPERATION........................5 5.1. PUSH BUTTON..............................5 5.2. LED ICON................................6 5.3. DISPLAY DESCRIPTION..........................6 5.4. OPERATION................................ 7 5.4.1.
  • Page 3: Summary

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. 1. SUMMARY The Module LXC706 is an small Automatic Engine Control Module. It selects 3 kinds of working state(Manual, Auto, Stop), can pass panel light touch buttons artificially start/stop genset, also can...
  • Page 4: Specification

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd.  With 3 working state: manual, automatic, stop.  Through the software setting of controllers can be set to the engine controller (not choose the power voltage input), suitable for control of pump unit.
  • Page 5: Display Symbol Amd Operation

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. Working Conditions Temperature:(-25~+70)ºC Relative humidity:(20~90)% Storage Conditions Temperature:(-30~+80)ºC IP55:When waterproof rubber seal installed between the controller and panel fascia Protection Level IP42:When waterproof rubber seal is not installed between the controller and panel fascia Object:input/output/power...
  • Page 6: Led Icon

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. 5.2. LED ICON Symbol Defined Symbol Defined High Temperature Automatic state Low Oil Press Stop state Over Speed Manual states Under speed Generator voltage Emergency Stop Battery voltage High voltage Amount of fuel...
  • Page 7: Operation

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. Oil pressure,Water temperature Liquid level %, Total running time Parameter Settings 5.4. OPERATION Module has three states: stop state 、man state 、auto state 5.4.1. Man Start When push Man start button ,preheat will first output, and start preheat delay, when preheat delay is end, fuel output 1 second, preheat output will stop, and crank output is start.Here engine...
  • Page 8: Stop State

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. NOTE: During the starting delay period, the fuel output disconnect. 3 seconds after entering  the starting delay process, pre-heat and ETS output.After the end of the starting delay period, ETS output disconnect. Fuel output and pre-heat output disconnect before starting.
  • Page 9: Parameters Table(Only Adjust Via Pc)

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. Emergency Stop: When emergency stop input, ETS solenoid stop immediately output, and  then fuel disconnect, preheat and start signal emit emergency stop alarm signal. Gen Over Voltage: When the continuous sampling voltage higher than the preset value, at ...
  • Page 10 LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. This is the amount of time that the start Idle speed is Start idle time (0-3600)S held active.These allow the engine to hold low speed. Warming up (0-3600)S delay Cooling delay...
  • Page 11 LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. When battery voltage has fallen below the set value Battery Under and remains for 20s, It will initiate a warning alarm Voltage (4.0-30.0)V 8.0V signal. Only warning and not to shutdown the (Warning)...
  • Page 12: Programmable Output (Table 2)

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. Disconnect When engine speed higher than the set value, starter (0-3000)RPM 360RPM Engine Speed will be disconnected. Disconnect Oil When generator oil pressure higher than the set value, (0-400)kPa 200kPa Pressure starter will be disconnected.
  • Page 13: Sensor Select (Table 4)

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. When this signal is effective and normal operation, If the temperature is too high, controller high-speed When cooling delay until after the downtime; When this signal temperature is too is invalid, If there is high temperature, the controller high downtime directly to the high-speed stop.
  • Page 14: Conditions Of Crank Disconnect

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. 8. CONDITIONS OF CRANK DISCONNECT Pictured above,select the desired options,can be selected or not selected  There are 4 conditions to make starter disconnected with engine,that is,speed sensor, generator frequency ,Charge D + and engine oil pressure. They all can be used separately. We...
  • Page 15: Terminal

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. 5) press the enter the parameter setting state, the first digit flashing, set of numerical methods with the same password input method. Password input interface: Parameter Settings interface: Matters needing attention:...
  • Page 16: Case Dimensions

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd.  Terminal 10(L)、11(N):Alternator Input.  Terminal 12(Idle Output):Idle speed control output port (B+,1A).  Terminal 13(Stop Output):ETS output (B+ ,1A).  Terminal 14(Configurable Output3):Configurable output, (B+, 1A).  Terminal 15( D+):Connect to charging starter’s D+ terminal. If there is no this terminal, then be hang up.
  • Page 17: Typical Connections

    LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co.,Ltd. 12. TYPICAL CONNECTIONS 13. PRODUCT PACKAGING Dongguan Tuancheng Automation Equipment Co.,LTD. This product should be following sets: Tel:8+86-769-33263276 Fax:+86-769-23166296 (1) 1 piece of controller model LXC706; http://dgfeirui.en.alibaba.com http://www.lixise.net (2) 2 piece of fixed cards;...