Page 1
5 to close magnetic sensor) 2015-02-09 Add LXC39X0 introduction Application picture updated 2015-03-19 LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 1 of 28 ...
Page 2
Indicates a procedure or practice, which could result in injury to personnel or loss of life if not followed correctly. WARNING LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 2 of 28 ...
Dongguan Tuancheng Automation Equipment Co.,LTD. 1. Summary LXC31X0 Series automation controller uses 32-bit ARM processor, the module is realized intelligent generator control technology.There are used for genset automation and monitor control system of single unit to achieve automatic start/stop, data measurement, alarm protection.It fit with LCD display, optional languages interface (Chinese, English, Spanish and Russian), and it is reliable and easy to use.It’s...
Shift the cursor up or increase the set value in parameter setting menu. Scrolls the screen down; Down/Decrease Shift the cursor down or decrease the set value in parameter setting menu. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 6 of 28 ...
Generator is placed into its standby mode after its complete stop. Otherwise, fail to stop alarm is initiated and the corresponding alarm information is displayed on LCD. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 8 of 28 ...
Charge Alt value, it will initiate a warning alarm and the corresponding alarm information will Failure be displayed on LCD. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 9 of 28 ...
Gen Under value, it will initiate a shutdown alarm and the corresponding alarm information will Voltage be displayed on LCD. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 10 of 28 ...
Compared with LXC3X20, LXC3X10 has no Mains AC Voltage input terminals. The rear panel of LXC3X10 and LXC3X20 is as below. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 11 of 28 ...
Page 12
Common terminal of auxiliary output 4 and 5. Connected to U-phase of generator (2A fuse is Gen U Phase Sensing 1.0mm recommended) LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 12 of 28 ...
Connected to N-wire of mains (LXC3X10 without) RS232 public grounded 0.5mm Recommended to use shielded cable, single-grounded RS232 RX 0.5mm shield(LXC31X0 series:no this function) RS232 TX 0.5mm Controller directly through the USB line connected to the USB Interface computer for parametric programming.
Mains Over Voltage is active. When set the value (30-620)V Voltage as 620V, the controller does not detect over voltage signal. Back lash: 10V(delay of 1 second) LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 14 of 28 ...
Page 15
(When genset has no magnetic sensor,please set to 5 to close magnetic sensor) Gen Abnormal (0-20.0)s The alarm delay of generator over voltage and LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 15 of 28 ...
Page 16
When battery voltage has fallen below the set (4-30)V Voltage(Warning) value and remains for 20s, It will initiate a warning LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 16 of 28 ...
Page 17
Never/From safety on/From Crank/Away. Digital Input 2Delay (0-20.0)s Delay output function. Digital Input 3 Type (0-29) Factory default: Remote Start. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 17 of 28 ...
Page 18
(0-1) Sensor Curve defined. Parameters Enter the parameter number, press confirm to selection quickly jump to the parameter setting items. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 18 of 28 ...
Aux Drop Speed and drop speeding output with control motor.When this switch is closed, raise speed output will turn off. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 19 of 28 ...
Action in period of gens normal to hi-speed cooling. Crank Success Pull in when detects a successful start signal. Mains OK Action when mains are normal. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 20 of 28 ...
Page 21
Low Oil Pressure Shutdown Action in low oil pressure shutdown. OP Sensor Open Action when oil pressure sensor are open circuit. 71-74 Aux Input 1-4Active LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 21 of 28 ...
(can be used in water pump set);if not select speed sensor in crank disconnect setting, the rotating speed displayed in controller is calculated by generator frequency and number of poles. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 22 of 28 ...
If there is no oil pressure sensor, but there is low oil pressure alarm switch, user must set the oil pressure sensor as “None”, otherwise, maybe low oil pressure shutdown occurs. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 23 of 28 ...
“Auxiliary Shutdown” (one end connect to normally open contact, the other end connect to ground). LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 24 of 28 ...
CAUTION!ICOM port must be connected to negative pole of battery. WARNING! When there is load current, transformer’s secondary side prohibit open circuit. LXC31X0/LXC39X0 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD. : T:+86 769-23162896 : F:+86 769-23166296 :www.lixise.com Page 27 of 28 ...