nilan Compact P User Manual page 35

Hide thumbs Also See for Compact P:
Table of Contents

Advertisement

114
TColdRet Open
115
TColdRet Short
116
Tevap Open
117
Tevap Short
122
Tmixing Open
123
Tmixing Short
124
SHW T-sensor Open
125
SHW T-sensor Short
126
SHW anode
127
TPres open
128
TPres short
200
LOM309 missing
600
Hi Pres
601
Low pres.
602
Leakage
603
Hi press
604
Frost protection
T14 Cold return temperature open connec-
tion.
T14 Cold return temperature short-cir-
cuited.
T23 Evaporator sensor temperature open
connection.
T23 Evaporator sensor temperature short-
circuited.
Tmixing temperature sensor open connec-
tion.
Tmixing temperature sensor shortcir-
cuited.
T21 Temperature sensor in SHW opne con-
nection.
T21 Temperature sensor in SHW shortcir-
cuited.
SHW anode failure.
T35 Temprerature sensor Pressure open
connection.
T35 Temperature sensor Pressure short-
circuited.
Controller is not Extended version
High pressure switch active.
Low pressure switch active.
Low pressure in brine - Brine pressure
switch active.
High pressure switch repeatedly active.
Temperature too low (state freeze protect)
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
The anode must be changed.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
Functionality of Extended version is
selected.
Exchange controller to the Extended ver-
sion or disable use of this functionality.
Check hot side pump/overflow valve on
high temperature side. Check if there is air
in the hot side water. Check if filter is
blocked on the hot side.
The unit restarts when the pressure drops
below high pressure switch lowlimit again.
After 3rd cut-out the alarm must be
acknowledged to start the unit again.
Check refrigerant charge, expansion valve
and evaporator for ice. Check fan for
obstacles on an air to water evaporator.
The alarm must be acknowledged to start
the unit again.
Leakage check of the brine system.
The alarm must be acknowledged to start
the unit again.
Check hot side pump/overflow valve on
high temperature side.
The alarm must be acknowledged to start
the unit again.
Heat pump and electrical heater running
full capacity.
Check that setting are not turned off.
35