> Low temp. compr. start
> Level winter low
> Temperature winter low
Condenser curve control
Supply air [%]
120
100
1
80
60
40
20
0
36
38
28
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
2
2
40
42
44
Condenser temperature [°C]
0  -15 °C / Off / 0  15 °C
Off
Here you indicate whether the heat pump is to start up at low
outdoor temperatures, even if heating is not required.
Off means that the function has been deactivated.
Level 1 / Level 2 / Level 3 / Off
Off
Here you specify at what fan speed level you want the ventila-
tion unit to operate at low outdoor temperatures.
Off means that the function has been deactivated.
-20  10 °C
0 °C
Here you specify at which outdoor temperature the "Winter low"
function is to be activated.
3
3
46
48
50
4
52