Trane 4TXM2318BF300AA Service Manual page 93

Table of Contents

Advertisement

3. Refrigerant piping work
1). Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the tor
wrenches. Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping
gas.
Flare nut fightening torque
Flare nut for Ø6.35
14.2-17.2N.m (144-175kgf.cm)
Flare nut for Ø9.52
32.7-39.9N.m (333-407kgf.cm)
Flare nut for Ø12.7
49.5-60.3N.m (505-615kgf.cm)
Flare nut for Ø15.88 61.8-75.4N.m (630-769kgf.cm)
Valve cap tightening torque
Liquid pipe 26.5-32.3N.m(270-330kgf.cm)
Gas pipe 48.1-59.7N.m(490-610kgf.cm)
2) To prevent gas leakage, apply refrigeration oil on both inner and outer surfaces of the flare. (Use refrigeration oil
for R410A)
4. Purging air and checking gas leakage
When piping work is completed, it is necessary to purge the air and check for gas leakage.
1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the
environment.
4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerents may damage
the vacuun pump or the unit.
• If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,
then charge additional refrigerant.
• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque.
Connect projection side of charging hose(Which comes from gauge manifold) to gas stop valve's service port.
Fully open gauge manifold's low-pressure valve(Lo) and completely close its high-pressure valve(Hi).
Apply vacuum pumping. Check that the compound pressure gauge reads-0.1MPa(-76cmHg).
Close gauge manifold's low-pressure valve(Lo) and stop vacuum pump.
(Leave as is for 4-5 minutes and make sure the coupling meter needie does not go back.
If it does go back, this may indicate the presence of moisture or leaking from connecting parts. After inspecting
all the connection and loosening then retightening thenuts, reqeat steps 2-4. )
Turn the liquid stop valve's rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Using soapy water, check for gas leakage from indoor unit's flare and outdoor unit's flare and valve rods.
Disconnect charging hose from gas stop valve's service port, then fully open liquid and gas stop valves.
Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the
specified torques. See "3 Refrigerant piping " on page 6 for details.
Service port cap tightening torque
10.8-14.7N.m(110-150kgf.cm)
WARNING
(High-pressure valve subsequently requires no operation.)
Evacuation for at lease 1 hour is recommended.
Remove covers from liquid stop valve and gas stop valve.
Close it after 5 seconds, and check for gas leakage.
After the check is complete, wipe all soapy water off.
(Do not attempt to turn valve rodj beyond its stop.)
91