Trane 4TXM2318BF300AA Service Manual page 140

Table of Contents

Advertisement

[20] Indoor Thermal Overload
If system is lack of refrigerant
If PMV coil is connection well
If sensor terminal is
fixed well
N
If sensor resistor /
characteristic is proper
Y
If indoor air passage is
patency
Y
N
If stop valve is open
Y
Y
If ambient
temperature is too
high
N
Reconnect
N
Replace sensor
N
Modify air passage
Y
Charge refrigerant
N
Check the system piping
N
Reconnect
N
Repalce PCB
138

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents