Installation - Trane 4TXM2318BF300AA Service Manual

Table of Contents

Advertisement

3.5 Installation

4MXD2309BF0R0AA 4MXD2312BF0R0AA 4MXD2318BF0R0AA 4MXD2324BF0R0AA
The Machine Is Adaptive In Following Situation
1. Applicable ambient temperature range:
Cooling
Heating
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified
person.
3. If the fuse on PC board is broken please change it with the type of T3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The breaker of the air conditioner should be all pole switch, and the distance between its two contacts should be
no less than 3mm. Such means for disconnection must be incorporation in the fixed wiring.
6. The installation height of the indoor unit is recommended from 2.5m to 2.7m.
7. The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded,
the diameter of the wire should be enlarged according to the local wiring standard.
8. The waste battery shall be disposed properly.
9. We can get the 4 different ESP through adjust the indoor unit PCB SW1 4 and SW1 5, please refer below:
[1]
[2]
Attention: Cut off the power supply to adjust the SW14, and SW15, or else the operation is invalid.
Parts and Functions
4MXD2309BF0R0AA
4MXD2312BF0R0AA
4MXD2318BF0R0AA
4MXD2324BF0R0AA
Heating
Outdoor Temperature
Indoor Temperature
Outdoor Temperature
SW01
[3]
[4]
0
0
1
1
Max. DB/WB
Min. DB/WB
Max. DB/WB
Min. DB/WB
Max. DB/WB
Min. DB/WB
Max. DB/WB
Min. DB/WB
[5]
[6]
0
1
0
1
31
32/23 ° C
18/14 ° C
46/24 ° C
18 ° C
27 ° C
15 ° C
24/18 ° C
15 ° C
Static
[7]
[8]
Pressure
0Pa
10Pa
20Pa
30Pa

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents