5.6 Limitation Values on Pipe lnstallation

4TXM2318BF300AA 4TXM2324BF300AA
The piping length information, please refer the following table.
Item
Unit
A,B,C Liquid Pipe mm
A,B,C Gas Pipe
mm
L1 (One Way)
m
L2 (One Way)
m
L3 (One Way)
m
L1+L2+L3
m
m
h
m
H+
m
m
H-
m
Description
Size of the liquid side connection pipe
Size of the gas side connection pipe
Max.piping length between IU and OU of the way
Max.piping length between IU and OU of the way
Max.piping length between IU and OU of the way
Total liquid piping length
Drop between every two indoor units when the location of
the outdoor unit is among indoor units
Drop between every two indoor units when the location of
the outdoor unit is at one side of indoor units
Drop between the outdoor unit and the indoor unit
Drop between the outdoor unit and the indoor unit when the
location of outdoor unit is among the indoor units
Drop between the outdoor unit and the indoor unit when the
location of outdoor unit is at one side of indoor units
82
Standard
Maximum
φ6.35
/
φ9.52
/
≤ 10
≤ 25
≤ 10
≤ 25
≤ 10
≤ 25
18BF<30
≤ 30
24BF<50
≤ 1
≤ 15
≤ 1
≤ 7.5
≤ 5
≤ 15
≤ 5
≤ 7.5
≤ 5
≤ 15