Download Print this page

Siemens FDCL181 Product Manual page 2

Line separator

Advertisement

Application
Structure
2
Building Technologies
Fire safety and security products
Protection of different branches from breaking down at the same time due to a short
l
circuit.
In a loop line connection, up to 32 devices can be connected between two isolators.
l
In a stub line connection, up to 32 devices can be connected to one isolator.
l
The module consists of the module carrier, the printed circuit board and the cover. The
printed circuit board includes two LEDs to indicate isolating/localization status.
To protect the modules from environmental influences, housing FDCH221 is
Fig.1 Overview