Goodman AMVS96U Service And Troubleshooting page 35

Single stage variable speed ultra-low nox gas furnaces and accessories
Table of Contents

Advertisement

TROUBLESHOOTING
Symptom
Furnace operates at reduced
performance or operates on
low stage when high stage is
expected
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to Operate
LED Status
Fault Description

Airflow is lower than demanded
Analog Pressure Sensor
Reference Error. APS reference
1
is out of the range (5.0+/-0.2)V
for 5 seconds
Analog Pressure Sensor Null
1
Error. Inconsistent Pressure
reading with inducer OFF
Analog Pressure Sensor Span
1d
Error. Inconsistent pressure
reading with inducer ON
Analog Pressure Error (Blocked
1
Vent Error)
Analog Pressure Sensor, Input
1
Error
Corrective Actions
Check filters for blockage, clean filters or remove
obstruction
Check ductwork for blockage, remove
obstruction and verify all registers are fully open
Verify ductwork is appropriately sized for system,
resize and/or replace ductwork if necessary
Verify electrical connections to pressure sensor
Verify electrical connections to pressure sensor
Verify electrical connections to pressure sensor
Need to check the APS Sensor or its connection
if this error is occurred. The failure conditions
occur as per the following for 5 seconds:
1. The vent is blocked, and the pressure could not
reach (lower than)
the target pressure when inducer stayed at
maximum RPM which
stored in Shared Data.
2. The vent is blocked, and the pressure could not
reach (higher than)
the target pressure when inducer stays at the
minimum RPM
(Pressure Switch Min Limit).
3. APS fault causes the pressure fixed at a value
lower than the target
pressure when inducer stayed at maximum RPM
which stored in
Shared Data.
4. APS fault causes the pressure fixed at a value
higher than the target
pressure when inducer stayed at minimum RPM
(Pressure Switch
Min Limit).
Check the APS Sensor or its connection if this
error is occurred. APS input voltage is out of the
below ranges for 5 seconds.
1. If 2" is selected, the voltage range shall be from
(0.25-0.06)V to (4+0.06)V.
2. If 4" is selected, the voltage range shall be from
(0.5-0.06)V to (4.5+0.06)V.
35